Abstract
Power electronics converters applied in domestic or similar installations may utilize current delay (phase) angle control to change the level of transferred power. Due to application of such types of converters, earth fault current in the installation may be strongly distorted. The current distortion level depends on a value of current delay angle. This delay angle also influences the tripping threshold of residual current devices. In this paper, computer modelling of the impact of current delay angle on behaviour of residual current devices is conducted. Results of laboratory tests of the tripping of residual current devices are discussed. Conclusions regarding electrical safety are presented as well.
Citations
-
1
CrossRef
-
0
Web of Science
-
3
Scopus
Authors (2)
Cite as
Full text
full text is not available in portal
Keywords
Details
- Category:
- Conference activity
- Type:
- materiały konferencyjne indeksowane w Web of Science
- Title of issue:
- 2017 International Conference on Information and Digital Technologies (IDT) strony 90 - 94
- Language:
- English
- Publication year:
- 2017
- Bibliographic description:
- Czapp S., Horiszny J..: The effect of current delay angle on tripping of residual current devices, W: 2017 International Conference on Information and Digital Technologies (IDT), 2017, ,.
- DOI:
- Digital Object Identifier (open in new tab) 10.1109/dt.2017.8024277
- Verified by:
- Gdańsk University of Technology
seen 123 times