Magnetic and capacitive couplings influence on power losses in double circuit high voltage overhead transmission line
Abstract
Purpose – The paper aims to discuss problems of power and energy losses in a double-circuit overhead transmission line. It was observed from energymeters’ readings, that in such a line, active power losses can be measured as “negative”. The “negative” active power losses appear when the active power injected to the circuit is lower than the active power received at the circuit end. The purpose of this paper is to explain this phenomenon. Theoretical considerations based on mathematical model of the transmission line of pi-type confirming that effect are presented. Power losses related to series impedance of the line and to shunt admittance are calculated. The theoretical considerations are confirmed by measurements done on the real transmission line.
Citations
-
3
CrossRef
-
0
Web of Science
-
2
Scopus
Authors (7)
Cite as
Full text
- Publication version
- Accepted or Published Version
- DOI:
- Digital Object Identifier (open in new tab) 10.1108/COMPEL-09-2016-0417
- License
- open in new tab
Keywords
Details
- Category:
- Articles
- Type:
- artykuł w czasopiśmie wyróżnionym w JCR
- Published in:
-
COMPEL-THE INTERNATIONAL JOURNAL FOR COMPUTATION AND MATHEMATICS IN ELECTRICAL AND ELECTRONIC ENGINEERING
no. 36,
edition 3,
pages 751 - 763,
ISSN: 0332-1649 - Language:
- English
- Publication year:
- 2017
- Bibliographic description:
- Klucznik J., Lubośny Z., Dobrzyński K., Czapp S., Kowalak R., Trębski R., Pokora S.: Magnetic and capacitive couplings influence on power losses in double circuit high voltage overhead transmission line// COMPEL-THE INTERNATIONAL JOURNAL FOR COMPUTATION AND MATHEMATICS IN ELECTRICAL AND ELECTRONIC ENGINEERING. -Vol. 36, iss. 3 (2017), s.751-763
- DOI:
- Digital Object Identifier (open in new tab) 10.1108/compel-09-2016-0417
- Verified by:
- Gdańsk University of Technology
seen 131 times