Voltage Harmonic Distortion Measurement Issue in Smart-Grid Distribution System - Publikacja - MOST Wiedzy

Wyszukiwarka

Voltage Harmonic Distortion Measurement Issue in Smart-Grid Distribution System

Abstrakt

This paper presents the investigation results ofvoltage harmonic transfer accuracy problems through voltagetransformers which are widely used in power quality monitoringsystems in medium and high voltage grids. A simplified lumpedparameters circuit model of the voltage transformer is presentedand verified by simulation and experimental investigations. Anumber voltage transformers typically used in medium voltagegrid has been tested in the conducted electromagnetic inter-ference frequency range up to 30 MHz. The obtained resultsconfirm that broadband voltage transfer function of the voltagetransformer usually exhibits various irregularities which areprimarily associated with voltage transformer winding parasiticcapacitances.

Cytowania

  • 1 3

    CrossRef

  • 0

    Web of Science

  • 1 5

    Scopus

Cytuj jako

Pełna treść

pełna treść publikacji nie jest dostępna w portalu

Słowa kluczowe

Informacje szczegółowe

Kategoria:
Aktywność konferencyjna
Typ:
materiały konferencyjne indeksowane w Web of Science
Tytuł wydania:
Asia-Pacific Symposium on Electromagnetic Compatibility APEMC'2012, Singapore, 21-24 May 2012 strony 841 - 844
Język:
angielski
Rok wydania:
2012
Opis bibliograficzny:
Łuszcz J., Smolenski R..: Voltage Harmonic Distortion Measurement Issue in Smart-Grid Distribution System, W: Asia-Pacific Symposium on Electromagnetic Compatibility APEMC'2012, Singapore, 21-24 May 2012, 2012, ,.
DOI:
Cyfrowy identyfikator dokumentu elektronicznego (otwiera się w nowej karcie) 10.1109/apemc.2012.6238024
Weryfikacja:
Politechnika Gdańska

wyświetlono 153 razy

Publikacje, które mogą cię zainteresować

Meta Tagi