Abstract
Residual current devices without integral overcurrent protection (RCCBs) are back-up protected by fuses or miniature circuit-breakers (MCBs). If the latter are used, special attention must be given to the coordination between an RCCB and an MCB. This paper indicates probable cases of the aforementioned devices coordination, in which back-up protection of the RCCB is not adequate. A laboratory test has shown that depending on the used type of the MCB, in case of value of short-circuit current close to the making and breaking capacity of an RCCB, excessive arc stress of the RCCB may occur. In case of short-circuit current of value close to the rated conditional short-circuit current of the RCCB, permissible values of peak current and Joule integral for the RCCB may be exceeded. All these stresses may limit electrical endurance of RCCBs.
Citations
-
1
CrossRef
-
0
Web of Science
-
1
Scopus
Authors (2)
Cite as
Full text
full text is not available in portal
Keywords
Details
- Category:
- Conference activity
- Type:
- publikacja w wydawnictwie zbiorowym recenzowanym (także w materiałach konferencyjnych)
- Title of issue:
- 2019 International Conference on Information and Digital Technologies (IDT) strony 75 - 79
- Language:
- English
- Publication year:
- 2019
- Bibliographic description:
- Czapp S., Kowalak D.: Remarks on the Subject of Back-Up Protection of Residual Current Devices// 2019 International Conference on Information and Digital Technologies (IDT)/ : , 2019, s.75-79
- DOI:
- Digital Object Identifier (open in new tab) 10.1109/dt.2019.8813461
- Verified by:
- Gdańsk University of Technology
seen 109 times