The effect of cable duct diameter on the ampacity of high-voltage power cables - Publication - Bridge of Knowledge

Search

The effect of cable duct diameter on the ampacity of high-voltage power cables

Abstract

The ampacity of power cables depends, among others, on the conditions of heat dissipation from the cable to the environment. Cables are usually laid directly in the ground, but in some sections, they may be placed in ducts, which adversely affects the ampacity of the cable line. The paper presents heat transfer phenomena for cables installed in pipe-type ducts filled with air. The effect of cable duct diameter on this ampacity is discussed. The results of the theoretical analysis have been validated by calculations performed with CYMCAP software. The comparison of the ampacity for air-filled vs. water- or bentonite-filled ducts is also included. The analyses and comparisons have shown that with an appropriate dimension of the duct, the simplest filling (with air) allows to obtain the ampacity not lower than when water or bentonite is used.

Citations

  • 1

    CrossRef

  • 0

    Web of Science

  • 1

    Scopus

Keywords

Details

Category:
Articles
Type:
artykuły w czasopismach
Published in:
Przegląd Elektrotechniczny pages 141 - 144,
ISSN: 0033-2097
Language:
English
Publication year:
2022
Bibliographic description:
Ratkowski F., Kołtun M., Czapp S.: The effect of cable duct diameter on the ampacity of high-voltage power cables// Przegląd Elektrotechniczny -Vol. 98,iss. 3 (2022), s.141-144
DOI:
Digital Object Identifier (open in new tab) 10.15199/48.2022.03.32
Verified by:
Gdańsk University of Technology

seen 203 times

Recommended for you

Meta Tags