Abstract
Recent trends in green energy development make that photovoltaics and electric vehicles are applied on an increasing scale. In both photovoltaic and electric vehicle charging installations, a significant value of DC component of the earth fault current may appear, which is a challenge, in particular, for commonly used residual current devices (RCDs). This paper presents results of the laboratory test on the operation of F-type RCDs – a type that is just beginning to appear in low-voltage installations. It has been checked how the tripping threshold of RCDs changes, if a smooth DC component is superimposed on the sinusoidal alternating current. It has been found that the F-type RCDs can operate very well even in the presence of a very high value of DC component.
Citations
-
0
CrossRef
-
0
Web of Science
-
1
Scopus
Authors (2)
Cite as
Full text
full text is not available in portal
Keywords
Details
- Category:
- Conference activity
- Type:
- publikacja w wydawnictwie zbiorowym recenzowanym (także w materiałach konferencyjnych)
- Language:
- English
- Publication year:
- 2022
- Bibliographic description:
- Czapp S., Tariq H.: Tripping of F-type RCDs for sinusoidal residual current with superimposed smooth DC component// / : , 2022,
- DOI:
- Digital Object Identifier (open in new tab) 10.1109/elektro53996.2022.9803395
- Verified by:
- Gdańsk University of Technology
seen 85 times