Thermal and economic investigation of straight and U-bend double tube heat exchanger with coiled wire turbulator - Publication - Bridge of Knowledge

Search

Thermal and economic investigation of straight and U-bend double tube heat exchanger with coiled wire turbulator

Abstract

Experimental research has been carried out for four individual heat exchanger constructions, i.e., plain double tube, turbulized double tube, plain U-bend and U-bend with turbulator. Tests were made for the water-water system. The study covered a wide measuring range, i.e., Re = 800–9000 – on the shell side, for a constant cold water temperature of 9 ◦C and hot water of 50 ◦C. The heat exchangers were made from copper tubes with external diameter of 10 mm and 18 mm respectively and wall thickness of 1 mm. The helicoidal vortex generator was made from brass wire with a diameter of 2.4 mm, coil diameter of 13 mm and pitch of 11 mm. For these geometries, the values of pressure drop, heat flux and heat transfer coefficient were determined. Wire coil turbulator increased the heat transfer coefficient (HTC) over 100% and pressure drop up by 100%. The comparison of heat transfer efficiency was performed based on the number of transfer units-effectivenes (NTU-ε) method. The modified construction achieved a similar efficiency. Economic analysis of wire coil turbulator was made to validate its use in the system. It showed that a coiled wire turbulator can greatly decrease the investment cost of the double tube heat exchanger while maintaining transferred heat at a constant level.

Citations

  • 0

    CrossRef

  • 0

    Web of Science

  • 3

    Scopus

Cite as

Full text

download paper
downloaded 133 times
Publication version
Accepted or Published Version
License
Creative Commons: CC-BY-NC-ND open in new tab

Keywords

Details

Category:
Articles
Type:
artykuły w czasopismach
Published in:
Archives of Thermodynamics no. 40, pages 17 - 33,
ISSN: 1231-0956
Language:
English
Publication year:
2019
Bibliographic description:
Andrzejczyk R., Muszyński T.: Thermal and economic investigation of straight and U-bend double tube heat exchanger with coiled wire turbulator// Archives of Thermodynamics -Vol. 40,iss. 2 (2019), s.17-33
DOI:
Digital Object Identifier (open in new tab) 10.24425/ather.2019.129540
Verified by:
Gdańsk University of Technology

seen 112 times

Recommended for you

Meta Tags