Time-current tripping characteristics of RCDs for sinusoidal testing current - Publication - Bridge of Knowledge

Search

Time-current tripping characteristics of RCDs for sinusoidal testing current

Abstract

Low-voltage electrical installations are verified initially – before being put into operation, as well as periodically – during their utilization. According to the IEC standards, the scope of the verification includes measurements of both the tripping current and the disconnection time of residual current devices (RCDs). Experiences in RCDs testing show that disconnection times of two or more similar RCDs can be quite different. Significant differences in disconnection times are also noticed for the same RCD in the consecutive trials. This paper presents the result of the test of twenty-four RCDs. Their real tripping current, as well as disconnection time, have been verified. Differences in the obtained values of disconnection times are commented, and their possible sources are indicated.

Citations

  • 0

    CrossRef

  • 0

    Web of Science

  • 1

    Scopus

Cite as

Full text

full text is not available in portal

Keywords

Details

Category:
Conference activity
Type:
publikacja w wydawnictwie zbiorowym recenzowanym (także w materiałach konferencyjnych)
Language:
English
Publication year:
2021
Bibliographic description:
Czapp S.: Time-current tripping characteristics of RCDs for sinusoidal testing current// / : , 2021,
DOI:
Digital Object Identifier (open in new tab) 10.1109/idt52577.2021.9497574
Verified by:
Gdańsk University of Technology

seen 60 times

Recommended for you

Meta Tags