Detection of inter-turn faults in transformer winding using the capacitor discharge method - Publication - Bridge of Knowledge

Search

Detection of inter-turn faults in transformer winding using the capacitor discharge method

Abstract

The paper presents results of an analysis of inter-turn fault effects on the voltage and current waveforms of a capacitor discharge through transformer windings. The research was conducted in the frame of the Facility of Antiproton and Ion Research project which goal is to build a new international accelerator facility that utilizes superconducting magnets. For the sake of electrical quality assurance of the superconducting magnet circuits, a measurement and diagnostic system is currently under development at Gdansk University of Technology (GUT). Appropriate measurements and simulations of the special transformer system were performed to verify the proposed diagnostic method. In order to take into account the nonlinearity and hysteresis of the magnetic yoke, a novel mathematical model of the transformer was developed. A special test bench was constructed to emulate the inter-turn faults within transformer windings.

Citations

  • 0

    CrossRef

  • 0

    Web of Science

  • 1

    Scopus

Keywords

Details

Category:
Articles
Type:
artykuły w czasopismach recenzowanych i innych wydawnictwach ciągłych
Published in:
Open Physics no. 15, edition 1, pages 979 - 983,
ISSN: 2391-5471
Language:
English
Publication year:
2017
Bibliographic description:
Michna M., Wilk A., Ziółko M., Wołoszyk M., Swędrowski L., Szwangruber P.: Detection of inter-turn faults in transformer winding using the capacitor discharge method// Open Physics. -Vol. 15., iss. 1 (2017), s.979-983
DOI:
Digital Object Identifier (open in new tab) 10.1515/phys-2017-0121
Verified by:
Gdańsk University of Technology