Abstract
This paper presents test results of a distance protection’s PSD power swing detection feature in ABB 670 series relays. A RED670 relay was tested, which is part of the hydroelectric set protection in Żarnowiec Pumped Storage Plant. The power swing blocking feature’s performance was analysed on the basis of the results of object tests made with an Omicron digital tester. Also presented are simulation results that illustrate the PSD feature’s response to power swings caused by a disturbance in the power system. It is also shown how a distance protection may react to the same fault, depending on its settings.
Authors (2)
Cite as
Full text
download paper
downloaded 23 times
- Publication version
- Accepted or Published Version
- License
- open in new tab
Keywords
Details
- Category:
- Articles
- Type:
- artykuły w czasopismach recenzowanych i innych wydawnictwach ciągłych
- Published in:
-
Acta Energetica
pages 75 - 86,
ISSN: 2300-3022 - Language:
- English
- Publication year:
- 2012
- Bibliographic description:
- Łosiński M., Klucznik J.: Performance analysis of power swing blocking feature in ABB 670 series impedance relays// Acta Energetica. -., nr. 4/13 (2012), s.75-86
- Verified by:
- Gdańsk University of Technology
seen 133 times
Recommended for you
Power System Dynamics. Stability and Control. 3rd edition
- J. Machowski,
- Z. Lubośny,
- J. Białek
- + 1 authors
2020