prof. dr hab. inż. Zbigniew Lubośny
Employment
- Professor at Department of Electrical Power Engineering
Publications
Filters
total: 137
Catalog Publications
Year 2015
-
A new method of fault loop resistance measurement in low voltage systems with residual current devices
PublicationThis paper presents a new method of fault loop resistance measurement in low voltage systems with residual current devices. The method enables measuring fault loop resistance without nuisance tripping of residual current devices, by application an unconventional waveform of measurement current. It is important for proper verification of the effectiveness of protection against electric shock.
-
Effectiveness of the robust PSS design
PublicationThe paper discusses optimal PSS of synchronous generator synthesis. The optimal controller is an Hinf controller, what means that minimises Hinf norm of transfer function between the exogenous signals such as reference inputs and disturbances, and the error signals which are to be minimised to meet the control objective. The dynamic properties of the plant are shaped by choosing appropriate weighting function applied to the plant...
-
EHV transmission lines wires location on line operation issues - case studies
PublicationTransmission lines towers construction affects the line parameters and influences on its operation in the future. Misguided design of the tower can lead to serious problems such as overvoltages, electric arc extinction difficulties, voltage asymmetry, resonance phenomena or increasing of magnetic field near the line. The paper points out those threats on example of 400 kV double circuit overhead transmission line with shunt reactors....
-
Ekspertyza : Mapa rozwoju dyscypliny Elektrotechnika : Systemy Elektroenergetyczne
PublicationW publikacji przedstawiono trendy rozwojowe dyscypliny elektrotechnika opracowanej przez Komitet Elektrotechniki PAN.
-
Fractional-order Systems and Synchronous Generator Voltage Regulator
PublicationModern regulators of synchronous generators, including voltage regulators, are digital systems, in their vast majority with standard structures contained in the IEEE standard. These are systems described with stationary differential equations of integral order. Differential equations of fractional order are not employed in regulators for synchronous generator control. This paper presents an analysis of the possibilities of using...
-
Induced sheath voltages in 110 kV power cables – case study
PublicationThis paper considers electric shock hazard due to induced sheath voltages in 110 kV power cables. The purpose of this paper is to find an optimal configuration of the power cable system, taking into account electric shock hazard and ability of the system to transfer maximal power. A computer simulations on a computer model of the local power system, comprising high voltage power cables, were carried out. This model enables to analyse...
-
Influence of Shunt Compensation with SVC Devices on Resonance Risk in Power Systems
PublicationMany analyses are required to locate a new reactive power source in a power system. The choice of a location is a very complex matter which requires various aspects to be considered. Selecting a location also entails the necessity to assess it from the point of view of the selected compensator’s structure as well as the system’s performance in various states with the new device on. The paper presents the issues of assessing compensator...
Year 2012
-
A Paradigm for HV, MV, LV Distribution Grid Development Planning
PublicationIn the literature, including that relating to businesses in the energy (and power) sector, the concept of these organizations’ operating paradigm may be found. The paper discusses the concept of the paradigm, with a focus on the power grid development planning paradigm. Against this background, issues related to energy security and power systems development trends and problems are presented. A new paradigm is proposed for distribution...
Year 2004
-
Adaptacyjny neuronowy regulator generatora synchronicznego.
PublicationPrzedstawiono adaptacyjny neuronowy regulator generatora synchronicznego składający się z adaptacyjnego regulatora napięcia i adaptacyjnego stabilizatora systemowego minimalizujących zadane funkcje celu. Sygnał wyjściowy regulatora tworzony jest jako suma ważona obydwu regulatorów.
Year 2009
-
Analityczne określanie parametrów stabilizatora systemowego dla generatora synchronicznego ze statycznym układem wzbudenia
PublicationW artykule przedstawiono metodę obliczania parametrów stabilizatora systemowego dla generatorów synchronicznych ze statycznym układem wzbudzenia i regulacji napięcia.
-
Application examples of wide area monitoring for system operators withinh UCTE = Zastosowanie technologii WAMS w systemie UCTE
PublicationRozrost geograficzny systemów elektroenergetycznych zwiększa prawdopodobieństwo wystąpienia słabo tłumionych kołysań elektromechanicznych. W artykule omawia się zastosowanie systemu WAMS w celu wykrywania tego typu zjawisk i dalej w celu ich eliminacji.
-
Application exaples of wide area monitoring for system operators within UCTE
PublicationW referacie przedstawiono przykładowe zastosowania pomiarów uzyskiwanych w systemie WAMS dla potrzeb systemu elektroenergetycznego.
-
Farmy wiatrowe w systemie elektroenergetycznym / Z. Lubośny.
PublicationKsiążka porusza zagadnienia współpracy elektrowni i farm wiatrowych z systemem elektroenergetycznym.
-
Farmy wiatrowe w układach nadrzędnej regulacji napięcia i mocy biernej
PublicationW artykule przedstawiono koncepcję włączenia farm wiatrowych w proces regulacji napięcia i mocy biernej w węzłach wytwórczych i elektrownianych.
-
Farmy wiatrowe w układach regulacji nadrzędnej.
PublicationPrzedstawiono koncepcję włączenia farm wiatrowych w system nadrzędnej regulacji węzłów elektrownianych i sieciowych.
Year 2005
-
Analiza lokalizacji i parametrów stabilizatorów systemowych w KSE
PublicationW referacie przedstawiono metodę doboru parametrów i lokalizacji stabilizatorów systemowych. Metodę tą zastosowano do oceny trafności doboru stabilizatorów w krajowym systemie elektro-energetycznym, a następnie do doboru struktury, parametrów i lokalizacji "nowych" stabilizatorów systemowych. Obliczenia wykonano dla pełnego modelu matematycznego krajowego systemu przesyłowego.
-
Blackout initial disturbances in electric Power System searching
PublicationThe paper contains short survey of the blackouts that took place in the last few years. The sources and initial disturbances are discussed. The typical scenario of the disturbance, leading to blackout in the electrical power system are presented.Next, models of a power system eligible to considered topic are discussed. Finally the algorithm of the blackout initial disturbances in power system searching is presented.The consideration...
Year 2017
-
Analiza napięć indukowanych i strat mocy w kablach elektroenergetycznych wysokiego napięcia dla wybranych sposobów uziemienia żył powrotnych
PublicationDostarczanie mocy do centrów miast coraz częściej odbywa się z wykorzystaniem linii kablowych o napięciu 110 kV. To dogodny sposób zasilania, a praktycznie jedyny możliwy w przypadku gęstej zabudowy miejskiej. Kable wysokiego napięcia zawierają współosiową żyłę powrotną, w której podczas normalnej pracy oraz w stanach zakłóceniowych (podczas zwarć) mogą indukować się znaczne napięcia względem ziemi, co zagraża porażeniem i/lub...
-
Analiza napięć indukowanych w żyłach powrotnych kabli wysokiego napięcia dla ich wybranych konfiguracji
PublicationW żyłach powrotnych kabli wysokiego napięcia mogą indukować się znaczne napięcia względem ziemi przy przepływie prądów roboczych oraz prądów zwarciowych, co zagraża porażeniem i/lub uszkodzeniem zewnętrznej powłoki kabla. Wartości tych napięć zależą od sposobu ułożenia i długości kabli, sposobu uziemienia ich żył powrotnych, wartości prądu w żyłach roboczych, a także transpozycji żył roboczych i powrotnych. W artykule przedstawiono...
-
Analiza napięć indukowanych w żyłach powrotnych kabli wysokiego napięcia w wybranych konfiguracjach ich ułożenia
PublicationW żyłach powrotnych kabli wysokiego napięcia mogą indukować się znaczne napięcia względem ziemi przy przepływie prądów roboczych oraz prądów zwarciowych, co zagraża porażeniem i/lub uszkodzeniem zewnętrznej powłoki kabla. Wartości tych napięć zależą od sposobu ułożenia i długości kabli, sposobu uziemienia ich żył powrotnych, wartości prądu w żyłach roboczych, a także transpozycji żył roboczych i powrotnych. W artykule przedstawiono...
-
Analysis of Induced Voltages and Power Losses in High Voltage Power Cables for Selected Methods of Cables Sheaths Bonding
PublicationPower is increasingly supplied to city centres with 110 kV cable lines. This is a convenient way to supply power, and practically the only one possible in areas of dense urban development. A high-voltage cable contains a coaxial metallic sheath, in which in normal operation and in fault conditions (during short-circuits) significant line-to-earth voltages can be induced, which threatens electric shock and/or damage to the cable’s...
-
Harmonics produced by traction substations – computer modelling and experimental verification
PublicationVoltage and current harmonics have a detrimental effect on the components of a power system. Current harmonics may result in the overload and damage to power transformers. Voltage harmonics may result in, for example, damage to capacitor banks used to compensate reactive power. Devices which contribute to both current and voltage distortion include traction rectifiers. This paper presents results of the computer investigation of...
-
Identification of the customer meter assignment to phases in LV grid: Selected issues of UPGRID project realization
PublicationThe paper presents selected issues on the European UPGRID grant implemented by a consortium of companies from seven European states, including from Poland, on the monitoring and control of low voltage grid using measurement pre-registered data by smart AMI meters. The paper focuses on the issue of lack of information on the assignment of communal meters to individual phases.
-
Improving sensitivity of residual current transformers to high frequency earth fault currents
PublicationFor protection against electric shock in low voltage systems residual current devices are commonly used. However, their proper operation can be interfered when high frequency earth fault current occurs. Serious hazard of electrocution exists then. In order to detect such a current, it is necessary to modify parameters of residual current devices, especially the operating point of their current transformer. The authors proposed...
Year 2011
-
Application capabilities of the maximum distributed generation estimate methodology
PublicationThe paper presents application capabilities of the maximum distributed generation estimate methodology. This subject is an example of solutions to the problem that today face the transmission system operator and distribution system operators, which is related to the high saturation with wind power generation predicted for the near future.
Year 2014
-
Badanie działania sterownika telemechaniki z funkcją sygnalizatora zwarć w wykorzystaniem modelu referencyjnego sieci SN
PublicationPrzedmiotem opracowania jest analiza działania sterownika telemechaniki STGP-3 z funkcją sygnalizatora zwarć opracowanego przez Instytut Energetyki Oddział Gdańsk. Badania sterownika przeprowadzono w laboratorium Elektroenergetycznej Automatyki Zabezpieczeniowej Wydziału Elektrotechniki i Automatyki Politechniki Gdańskiej.
-
Calculation of Induced Sheath Voltages in Power Cables – Single Circuit System versus Double Circuit System
PublicationThis paper presents comparison of values of induced sheath voltages in power cable metallic sheaths when one or two cables per phase are used. Calculation of voltages is performed for various phase sequences of the power cables. Three types of the sheaths bonding and earthing are considered. Shock hazard and voltage stress of non-metallic outer sheath of cables are evaluated. The proposed, optimal configuration of the power cable...
-
Case studies of resonance phenomena in high voltage overhead power lines with shunt reactors
PublicationMisguided design of the towers of power transmission lines can lead to serious problems such as voltage asymmetry, overvoltages, electric arc extinction difficulties or resonance – in case of double circuit line with shunt reactors. The paper points out those threats on example of 400 kV double circuit overhead transmission line with shunt reactors.
-
Computer-aided Analysis of Induced Sheath Voltages in High Voltage Power Cable System
PublicationThis paper concerns the effect of configuration of high voltage power cables on induced voltages in their metallic sheaths. One, two or three cables per phase and phase sequence of the cables are considered. Computing of the voltages was performed for a normal operation and in case of earth fault. Various ways of the sheaths bonding are considered as well. Shock hazard and voltage stress of non-metallic outer sheath of cables are...
-
Detection of high frequency current components by residual current devices
PublicationThe negative impact of current harmonics on the main components of residual current devices is presented. A solution for the improvement of the operation of residual current devices is proposed.
-
Elektroenergetyczna automatyka zabezpieczeniowa farm wiatrowych
PublicationKsiążka prezentuje zagadnienia związane z elektroenergetyczną automatyką zabezpieczeniową farm wiatrowych. Przedstawiono zasady doboru zabezpieczeń sieci farmy wiatrowej (w tym przekładników zabezpieczeniowych) oraz elementów systemu elektroenergetycznego przylegających do farmy wiatrowej. Rozważania powyższe poparto przykładem doboru zabezpieczeń, nastaw zabezpieczeń, przekładników prądowych i napięciowych zabezpieczeniowych dla...
-
Estimation of Selected Synchronous Generator Parameters Based on the Gradient Method
PublicationThe authors present a method for the estimation of synchronous generator model parameters using a gradient algorithm. The paper shows an example of model parameter estimation for a turbogenerator and hydrogenerator, based on the generator voltage time responses obtained during an active and reactive power rejection test.
-
Evaluation Of Single Pole Auto-Reclosing Effectiveness With Nonlinear Secondary Arc Model
PublicationThe paper discusses two evaluation methods of single pole auto-reclosing process effectiveness in HV transmission lines. Secondary arc current and recovery voltage results obtained by load flow calculation are compared to the results obtained by the time domain simulations. Moreover, a non-linear secondary arc implementation is presented. The authors indicate, that precise representation of secondary electric arc leads to more...
-
Induced Sheath Voltages In 110 Kv Power Cables – Case Study
PublicationThe paper considers shock hazard due to induced sheath voltages in 110 kV power cables. Various configurations of the metallic sheaths bonding and earthing (single-point bonding, both-ends bonding, cross-bonding) are analysed. Taking into account shock hazard and ability of the system to power transfer an optimal configuration is proposed.
Year 2016
-
Calculations of Short-Circuit Current Flows in Earth Wires of HV Lines
PublicationThis paper presents a method which enables calculating flows of short-circuit currents in earth wires of high voltage transmission lines, and its implementation in the form of a computer programme. The algorithm enables performing calculations for a double-fed line and starconnected lines (three terminal lines). The developed programme enables verifying dimensioning of earth wires in the context of their short-circuit thermal withstand...
-
Computer-aided analysis of resonance risk in power system with Static Var Compensators
PublicationStatic Var Compensators operation in a power system may significantly improve voltage profiles in nodes and the reactive power balance, as well as ensure greater system stability in emergency conditions. However these devices may be a cause of a resonance in the system. The aim of this paper is to call attention to the need to include resonance phenomena in a compensator’s location evaluation process. The analysis performed in...
-
Elektrownie wiatrowe a stabilność systemu Elektroenergetycznego
PublicationW pracy omówiono problematykę wpływu elektrowni wiatrowych na system elektroenergetyczny. Rozważano zagadnienia związane z pewnością generacji, rezerwowaniem mocy czynnej, regulacją napięcia i mocy, jakością energii, stabilnością napięciową, stabilnością lokalną, stabilnością globalną, zdolnością do uczestnictwa w obronie i odbudowie systemu elektroenergetycznego, itd.
-
Higher harmonics produced by traction substations – computer modelling and experimental verification
PublicationVoltage and current harmonics have a detrimental effect on the components of a power system. Current harmonics may result in the overload and damage to power transformers, although the rms value of load current does not exceed their current-carrying capacity. Voltage harmonics may result in, for example, damage to capacitor banks used to compensate reactive power. Devices which contribute to both current and voltage distortion...
-
Impact of configuration of earth continuity conductor on induced sheath voltages in power cables
PublicationIn high voltage power cable systems a problem of induced sheath voltages exist. Due to these voltages electric shock and damage of non-metallic outer sheath of the cables may occur. Exposure to voltage of the outer sheath may be very high in case of earth fault with high value of earth current. In order to reduce induced sheath voltages an earth continuity conductor (conductors) along power cables is applied. Configuration of this...
Year 2019
-
Cross-Bonding of MV Cable Lines for Energy Losses Decrease
PublicationCurrently, almost all medium voltage cable lines (MV) operate with the return wires earthed at both ends of the cable. Such a way of operation causes that during normal states of operation as well as during disturbances, e.g. short-circuits, in the return wires induce currents whose values mainly depend on the currents flowing in the phase wires. These currents in normal operating states are a source of additional energy losses...
-
Energy losses reduction in the medium voltage cable line – case study
PublicationThe paper presents an analysis of energy losses in a power cable system, which is composed of two 30 kV cable lines. This cable system is located at the seaside holiday area, so the load profile during a year is specific. Energy losses related to reactive power transmission, as well as to currents induced in the sheaths of the cables, are subject to analysis. Measurements were made in the system in order to prepare a computer model...
-
Hydro Power Plant in the Process of Voltage Control in the Electric Power System and the System Restoration
PublicationThe article covers selected issues related to the share of hydroelectric power in the process of rebuilding the power system after black-out and voltage control during that process. Selected results of measurements made during the creation of the transmission chain for the need to start a block of a thermal power plant from a hydroelectric power plant were presented.
Year 2018
-
Cross-border transmission line configuration influence on the electrical power and energy billing process
PublicationIn 2015 a connection between the Polish and Lithuanian power systems become fully operational. The connection consists of a 400 kV double circuit transmission line and a back-to-back HVDC substation located on the Lithuanian side. A magnetic couplings between the circuits of the transmission line cause that during power transmission a different values of active power losses are observed in both circuits. This situation may cause...
-
Delivery of Ancillary Services in Distribution Power Systems
PublicationOne of the technical and organizational challenges the power system faces in deregulated market conditions is to organize an ancillary services market. The growing share of distributed generation of variable (intermittent) energy sources and a change in the market position of consumers, causes the demand for distributed delivery of ancillary services. For this purpose, it is sought to use the ability of the regulatory measures:...
Year 2003
-
Ekwiwalentowanie farm wiatrowych
PublicationW artykule zaproponowano sposób modelowania i ekwiwalentowania dużych farm wiatrowych. Przedstawiono sposoby tworzenia modeli w celu ich wykorzystania do analiz stanów ustalonych i nieustalonych systemu elektroenergetycznego.
-
Isolation and restoration policies against power collapse.
PublicationPrzedstawiono zasady obrony systemów elektroenergetycznych przed tzw. blackout´em. Omówiono wielkości kryterialnych tych systemów, możliwości predykcji stanów zagrożeniowych oraz automatyki działające on line w celu zapobieżenia rozprzestrzeniania się zakłóceń i awarii w systemach elektroenergetycznych.
Year 2013
-
Estymacja wybranych parametrów modelu generatora synchronicznego z wykorzystaniem metody gradientowej rozmytej – referat konferencyjny
PublicationReferat prezentuje metodę estymacji parametrów modelu generatora synchronicznego z wykorzystaniem algorytmu gradientowego. Przedstawiono przykład estymacji parametrów modelu hydrogeneratora w oparciu o przebiegi napięcia generatora podczas dwóch testów: zrzutu mocy czynnej i zrzutu mocy biernej. Prezentowane analizy zostały wykonane w autorskim programie wykorzystującym środowisko modelowania PowerFactory firmy DIgSILENT.
-
Interior Point Method Evaluation for Reactive Power Flow Optimization in the Power System
PublicationThe paper verifies the performance of an interior point method in reactive power flow optimization in the power system. The study was conducted on a 28 node CIGRE system, using the interior point method optimization procedures implemented in Power Factory software.
Year 2020
-
Incomplete Cross-Bonding in the MV Line. Experience from the Operation of MV Single Cable Lines
PublicationCable lines are one of the basic components of power systems. Medium and high voltage cables mainly comprise a metallic sheath, which is concentric to the main core conductor. There are several operating schemes of such cable lines, which differ in the place of earthing of sheaths and the possible use of the sheaths and/or conductors crossing. The sheaths cross-bonding is typically done in two places of one cable line section,...
-
Integrated algorithm for selecting the location and control of energy storage units to improve the voltage level in distribution grids
PublicationThis paper refers to the issue that mainly appears in distribution grids, where renewable energy sources (RES) are widely installed. In such grids, one of the main problems is the coordination of energy production time with demand time, especially if photovoltaic energy sources are present. To face this problem, battery energy storage units (ESU) can be installed. In recent years, more and more attention has been paid to optimizing...