Influence of span length and impulse front time on earthing measurement accuracy of power line towers
Abstract
The article discusses the issue of measuring and assessing the features of power line tower earthings using fast-changing waveform. The study analyses the effect of impulse front time and the line span length on errors made during these measurements using impulse meters. It has been found that the assessment conditions similar to the static measurement results occur for the use of 4 μs current impulses and such procedure is useful for evaluating power line tower earthings.
Citations
-
0
CrossRef
-
0
Web of Science
-
0
Scopus
Author (1)
Cite as
Full text
download paper
downloaded 28 times
- Publication version
- Accepted or Published Version
- DOI:
- Digital Object Identifier (open in new tab) 10.15199/48.2016.02.32
- License
- open in new tab
Keywords
Details
- Category:
- Articles
- Type:
- artykuły w czasopismach recenzowanych i innych wydawnictwach ciągłych
- Published in:
-
Przegląd Elektrotechniczny
pages 112 - 114,
ISSN: 0033-2097 - Language:
- English
- Publication year:
- 2016
- Bibliographic description:
- Wojtas S.: Influence of span length and impulse front time on earthing measurement accuracy of power line towers// Przegląd Elektrotechniczny. -., nr. 2 (2016), s.112-114
- DOI:
- Digital Object Identifier (open in new tab) 10.15199/48.2016.02.32
- Verified by:
- Gdańsk University of Technology
seen 110 times
Recommended for you
Impulse Impedance Measurements of Lightning Protection Earthings
- T. Horchue,
- W. Tangtheerajaroonwong,
- S. Wojtas
- + 1 authors
2019