Computer-aided Analysis of Induced Sheath Voltages in High Voltage Power Cable System
PublicationThis paper concerns the effect of configuration of high voltage power cables on induced voltages in their metallic sheaths. One, two or three cables per phase and phase sequence of the cables are considered. Computing of the voltages was performed for a normal operation and in case of earth fault. Various ways of the sheaths bonding are considered as well. Shock hazard and voltage stress of non-metallic outer sheath of cables are...
-
Safety issues referred to induced sheath voltages in high-voltage power cables – case study
PublicationLoad currents and short-circuit currents in high-voltage power cable lines are sources of the induced voltages in the power cables’ concentric metallic sheaths. When power cables operate with single-point bonding, which is the simplest bonding arrangement, these induced voltages may introduce an electric shock hazard or may lead to damage of the cables’ outer non-metallic sheaths at the unearthed end of the power cable line. To...
-
Induced sheath voltages in 110 kV power cables – case study
PublicationThis paper considers electric shock hazard due to induced sheath voltages in 110 kV power cables. The purpose of this paper is to find an optimal configuration of the power cable system, taking into account electric shock hazard and ability of the system to transfer maximal power. A computer simulations on a computer model of the local power system, comprising high voltage power cables, were carried out. This model enables to analyse...
-
Induced Sheath Voltages In 110 Kv Power Cables – Case Study
PublicationThe paper considers shock hazard due to induced sheath voltages in 110 kV power cables. Various configurations of the metallic sheaths bonding and earthing (single-point bonding, both-ends bonding, cross-bonding) are analysed. Taking into account shock hazard and ability of the system to power transfer an optimal configuration is proposed.
-
Impact of configuration of earth continuity conductor on induced sheath voltages in power cables
PublicationIn high voltage power cable systems a problem of induced sheath voltages exist. Due to these voltages electric shock and damage of non-metallic outer sheath of the cables may occur. Exposure to voltage of the outer sheath may be very high in case of earth fault with high value of earth current. In order to reduce induced sheath voltages an earth continuity conductor (conductors) along power cables is applied. Configuration of this...
-
Calculation of Induced Sheath Voltages in Power Cables – Single Circuit System versus Double Circuit System
PublicationThis paper presents comparison of values of induced sheath voltages in power cable metallic sheaths when one or two cables per phase are used. Calculation of voltages is performed for various phase sequences of the power cables. Three types of the sheaths bonding and earthing are considered. Shock hazard and voltage stress of non-metallic outer sheath of cables are evaluated. The proposed, optimal configuration of the power cable...
-
Efficient Analysis of Noise Induced in Low-Voltage Installations Placed Inside Buildings with Lightning Protection Systems
PublicationThis paper describes an efficient approach to the broadband analysis of lightning protection systems (LPSs) using the method of moments (MoM) implemented in the frequency domain. The adaptive frequency sampling (AFS) algorithm, based on a rational interpolation of the relevant observable (e.g., voltage, current, electric or magnetic field) which describes the properties of the LPS, is employed to reduce the number of samples computed...
-
Analysis of Induced Voltages and Power Losses in High Voltage Power Cables for Selected Methods of Cables Sheaths Bonding
PublicationPower is increasingly supplied to city centres with 110 kV cable lines. This is a convenient way to supply power, and practically the only one possible in areas of dense urban development. A high-voltage cable contains a coaxial metallic sheath, in which in normal operation and in fault conditions (during short-circuits) significant line-to-earth voltages can be induced, which threatens electric shock and/or damage to the cable’s...
-
Simulation of influence of the air gap asymmetryon voltage waveforms of a synchronous machine
PublicationResults of simulation of a synchronous generator with the air gap asymmetry characterised by eccentricity are presented in the paper. The Lagrange's energy method has been used in derivation of the model equations. Analysis of influence of the air gap asymmetry on characteristics of self and mutual inductances of windings, as well as analysis of induced voltage waveforms as a function of the air gap asymmetry have been performed....
-
Incomplete Cross-Bonding in the MV Line. Experience from the Operation of MV Single Cable Lines
PublicationCable lines are one of the basic components of power systems. Medium and high voltage cables mainly comprise a metallic sheath, which is concentric to the main core conductor. There are several operating schemes of such cable lines, which differ in the place of earthing of sheaths and the possible use of the sheaths and/or conductors crossing. The sheaths cross-bonding is typically done in two places of one cable line section,...