Voltage fluctuations on the main switchgear of the industrial power system supplying the rolling mill motors_part_2
Opis
The dataset presents the voltage waveforms on the bus bars of the main switchgear of the industrial power network for the supply of rolling mills. The data was recorded during an experiment whose purpose was to determine a level of short-term and long-term flicker caused by voltage fluctuations. In the virtual application of flickermeter, a hardware (acquisition of measuring data) and a software (computer data processing and graphical interface ) part can be distinguished. The attached dataset contains raw data at the output of the hardware part of the flickermeter.
The measurements were carried out in one of the Polish steel mills, in the GST- 6 switching station, on medium voltage (6 kV) switchgear rails in measurement field 2a using voltage transformers. The voltage value on the secondary side of the transformers was 100/root(3) V (a phase voltage). Field 3a of the switchboard supplies the rolling mill motor, whose operation causes voltage fluctuations. The scheme of the switchgear with the measuring point marked is shown in Figure 1. The measurement six five hours from 11:10 to 17:10. After the initial rolling period (until 11:30), there was a break in the rolling mill operation until about 14:20.
Measurements were performed using a measurement system that allows simultaneous measurement of three phase-to-phase or two-phase voltages. In the hardware part of the measuring system (Figure 2), the signal is first pre-conditioned. The analogue signal processing consists of matching the level of the measured signal to the inputs of the optoisolation amplifier, which ensures the separation of the high voltage signal. Then low-pass filtration through a set of anti-aliasing filters is carried out. The formation of the output digital signal from the analogue signal takes place in the A/D converter with a 16-bit resolution and a sampling rate of up to 20 kS/s.
The sampling frequency is equal to 20 000 Hz and is inserted in the first row of the attached files.
The file steel_mill_1 and steel_mill_2 contain the results of measurements that started at 11:10 and lasted about 60 and 6 minutes respectively. These files are placed in the dataset [Pałczyńska, B., & Tarasiuk, T. (2020). Voltage fluctuations on the main switchgear of the industrial power system supplying the rolling mill motors [Data set]. Gdańsk University of Technology. https://doi.org/10.34808/wv44-3z34]
The file steel_mill_3 and steel_mill_4 contain the results of measurements that started at 14:30 and lasted about 61 and 45 minutes respectively.
Figure 1. The scheme of the switchgear with the measuring point marked
Figure 2. The hardware part of the measurement system
Plik z danymi badawczymi
hexmd5(md5(part1)+md5(part2)+...)-{parts_count}
gdzie pojedyncza część pliku jest wielkości 512 MBPrzykładowy skrypt do wyliczenia:
https://github.com/antespi/s3md5
Informacje szczegółowe o pliku
- Licencja:
-
otwiera się w nowej karcieCC BYUznanie autorstwa
- Dane surowe:
- Dane zawarte w datasecie nie zostały w żaden sposób przetworzone.
Informacje szczegółowe
- Rok publikacji:
- 2021
- Data zatwierdzenia:
- 2021-06-25
- Data wytworzenia:
- 2000
- Język danych badawczych:
- angielski
- Dyscypliny:
-
- Automatyka, elektronika i elektrotechnika (Dziedzina nauk inżynieryjno-technicznych)
- DOI:
- Identyfikator DOI 10.34808/dx3f-0a72 otwiera się w nowej karcie
- Seria:
- Weryfikacja:
- Politechnika Gdańska
Słowa kluczowe
Powiązane zasoby
- dane badawcze Voltage fluctuations on the main switchgear of the industrial power system supplying the rolling mill motors
- dane badawcze The short-term flicker severity level measured in the industrial power system supplying the rolling mill motors
- dane badawcze The instantaneous flicker sensation level measured in the industrial power system supplying the rolling mill motors
- dane badawcze A cumulative probability function of instantaneous flicker sensation values measured in the industrial power system supplying the rolling mill motors
Cytuj jako
Autorzy
wyświetlono 148 razy