Calibration of NTC 10k thermistors in temperature of 100 C - Open Research Data - Bridge of Knowledge

Search

Calibration of NTC 10k thermistors in temperature of 100 C

Description

The presented data set is part of the research aimed at determining the actual characteristics of each thermistor in a package of twenty NTC10k type sensors.

The measurement system is shown in Fig. 1. A measurement system based on NI PXIe-1082Q (National Instruments Chassis), equipped with NI PXIe-8135 (Embedded Controller), NI PXIe-6341 (DAQ card) and NI SCB-68A (68-pin connector block), was used for the acquisition of measurement data. Eleven input channels of the DAQ card were used in the measurements. Channel 0 (ch_0) was used to measure the supply voltage. Sensors numbered 1 to 20 were tested in two parts, ten sensors per set. They were connected to the inputs of channels 1-10 (ch_1-ch_10) of the DAQ card.

Illustration of the publication

Fig. 1. The measurement setup

 

The conditioning unit for individual sensors is shown in Fig.2. These circuits are performed on connector block SCB-68A as the voltage dividers. For the set of ten thermistors, the supply voltage is measured in channel 0 (ch_0) of the DAQ card, and individual thermistors are connected to channels 1-10 (ch_i).

The thermistor set was placed in the T-704 thermocalibrator chamber at 100°C (confirmed by a digital temperature gauge DT-34 with an accuracy of 0.1°C).

Illustration of the publication

                                                                                                              Fig. 2. The sensor conditioning unit

The folder I100,0C  composed of 15 files 100,0Cx.lvm (where: x is from 0 to 14), contains the measurement results of supply voltage Uz (ch_0) (Fig.2) and voltages at the outputs of ten voltage dividers (ch_1 to ch_10), repeated in a series of 30 measurements for all 11 channels.

The measuring series was carried out also for the second package of ten thermistors. The folder was marked as II100,0C, containing the files II100,0Cx.lvm  (where: x is from 0 to 14).

Dataset file

temp_100.zip
38.6 kB, S3 ETag 0ae60189821373ce4456c226c6cc9503-1, downloads: 60
The file hash is calculated from the formula
hexmd5(md5(part1)+md5(part2)+...)-{parts_count} where a single part of the file is 512 MB in size.

Example script for calculation:
https://github.com/antespi/s3md5
download file temp_100.zip

File details

License:
Creative Commons: by 4.0 open in new tab
CC BY
Attribution
Raw data:
Data contained in dataset was not processed.

Details

Year of publication:
2021
Verification date:
2021-03-09
Creation date:
2021
Dataset language:
English
Fields of science:
  • Automation, electronic and electrical engineering (Engineering and Technology)
DOI:
DOI ID 10.34808/hexp-sy19 open in new tab
Series:
Verified by:
Gdańsk University of Technology

Keywords

References

Cite as

seen 327 times