Description

The presented dataset is part of research focusing on the assessment of metrological properties of the instrument,  Estimator/Analyzer (E/A v.2),  developed and made at the Faculty of Electrical Engineering, Department of Marine Electrical Power Engineering of Gdynia Maritime University. The attached dataset contains processed data expressing an active power distribution in a ship power station.

The measurement setup is shown in Fig. 1.  A measurement system based on NI PXIe-1062Q was used as a reference instrument for the E/A instrument performance assessment.

The dataset file was created on the base of the selected data derived from two files: E_A.txt (research data: Selected results of signal measurements in a ship power station with two generators working in parallel with the use of the Estimator/Analyzer instrument, R. Maśnicki D. Hallmann J. Mindykowski T. Tarasiuk M. Górniak M. Szweda, DOI:10.34808/dv88-sj58) and PXI.txt (research data: Selected results of measurements carried out in a ship power station with two generators working in parallel with the use of the NI PXIe-1062Q based measurement system, R. Maśnicki D. Hallmann J. Mindykowski T. Tarasiuk M. Górniak M. Szweda, DOI:10.34808/h2xb-8a23). Raw data from these files, after appropriate calculations and after time synchronization of the obtained results, were used to determine the parameters included in the attached file.

The individual rows of data contain the active power values designated with a time step of 200 ms using data obtained from the E/A instrument (P1 E/A and P2 E/A) as well as from the PXI system (P1 PXI and P2 PXI) during measurements in a ship power station with two operating generators G1 and G2. Since the active power E/A was calculated for the line voltages, and the active power PXI values were calculated using phase voltages, additional columns for power PXI values were added, corrected for the root of 3.

Illustration of the publication

Fig. 1. The measurement setup

Dataset file

dataset_sc1.rar
83.4 kB, S3 ETag d768f7c18cd8d9fa0fd832f803bc27e0-1, downloads: 68
The file hash is calculated from the formula
hexmd5(md5(part1)+md5(part2)+...)-{parts_count} where a single part of the file is 512 MB in size.

Example script for calculation:
https://github.com/antespi/s3md5

File details

License:
Creative Commons: by 4.0 open in new tab
CC BY
Attribution

Details

Year of publication:
2020
Verification date:
2020-12-17
Creation date:
2011
Dataset language:
English
Fields of science:
  • Automation, electronic and electrical engineering (Engineering and Technology)
DOI:
DOI ID 10.34808/3wk0-8b31 open in new tab
Verified by:
Gdańsk University of Technology

Keywords

References

Cite as

seen 143 times