Evaluation of applicability of classic methods of a fault loop impedance measurement to circuits with residual current devices - Publication - Bridge of Knowledge

Search

Evaluation of applicability of classic methods of a fault loop impedance measurement to circuits with residual current devices

Abstract

Measurement of fault loop impedance in low voltage grids and systems is in most cases performed to verify the effectiveness of protection against electric shock by automatic disconnection of supply. For the sake of measurement accuracy, it is advisable to perform it using large current. Unfortunately, in circuits with residual current devices which are very widely used nowadays, a large measurement current may trigger those devices unnecessarily. The study presents results of an investigation of residual current devices behaviour during measurements of fault loop impedance performed with selected measuring devices. The tests have been performed on circuits with residual current devices with a rated residual operating current IΔn = 30 mA, of AC and A type. Based on the performed tests and analyses, a method for measurement of fault loop impedance which does not unnecessarily trigger residual current devices has been proposed.

Citations

  • 0

    CrossRef

  • 0

    Web of Science

  • 0

    Scopus

Keywords

Details

Category:
Articles
Type:
artykuły w czasopismach recenzowanych i innych wydawnictwach ciągłych
Published in:
Acta Energetica pages 45 - 52,
ISSN: 2300-3022
Language:
English
Publication year:
2016
Bibliographic description:
Czapp S., Borowski K.: Evaluation of applicability of classic methods of a fault loop impedance measurement to circuits with residual current devices// Acta Energetica. -., nr. 3/28 (2016), s.45-52
DOI:
Digital Object Identifier (open in new tab) 10.12736/issn.2300-3022.2016305
Verified by:
Gdańsk University of Technology

seen 145 times

Recommended for you

Meta Tags