Abstract
This article presents a comparison between integer and non-integer order modelling of a synchronous generator, in the frequency domain as well as in the time domain. The classical integer order model was compared to one containing half -order systems. The half-order systems are represented in a Park d-q axis equivalent circuit as impedances modelled by half-order transmittances. Using a direct method based on the approximation of the half-order derivatives by the Grünwald–Letnikov definition, a state-space equation system was solved. For both models, a computational program written in Matlab software was used. For the purpose of time domain simulation, the machine models were connected to an electric load composed of an RL circuit. To validate and compare both models, simulation results of a three-phase short-circuit and a no-load voltage recovery were compared with corresponding measurements performed on a solid salient-pole synchronous generator of 125 kVA.
Citations
-
2
CrossRef
-
0
Web of Science
-
4
Scopus
Authors (4)
Cite as
Full text
- Publication version
- Accepted or Published Version
- License
- open in new tab
Keywords
Details
- Category:
- Articles
- Type:
- artykuły w czasopismach
- Published in:
-
ENERGIES
no. 13,
ISSN: 1996-1073 - Language:
- English
- Publication year:
- 2020
- Bibliographic description:
- Racewicz S., Kutt F., Michna M., Sienkiewicz Ł.: Comparative Study of Integer and Non-Integer Order Models of Synchronous Generator// ENERGIES -Vol. 13,iss. 17 (2020), s.4416-
- DOI:
- Digital Object Identifier (open in new tab) 10.3390/en13174416
- Verified by:
- Gdańsk University of Technology
seen 122 times