Voltage fluctuations on the main switchgear of the industrial power system supplying the rolling mill motors - Open Research Data - MOST Wiedzy

Wyszukiwarka

Voltage fluctuations on the main switchgear of the industrial power system supplying the rolling mill motors

Opis

The dataset presents the voltage waveforms on the bus bars of the main switchgear of the industrial power network for the supply of rolling mills. The data was recorded during an experiment whose purpose was to determine a level of short-term and long-term flicker caused by voltage fluctuations. In the virtual application of flickermeter, a hardware (acquisition of measuring data) and a software (computer data processing and graphical interface ) part can be distinguished. The attached dataset contains raw data at the output of the hardware part of the flickermeter.

The measurements were carried out in one of the Polish steel mills, in the GST- 6 switching station, on medium voltage (6 kV) switchgear rails in measurement field 2a using voltage transformers. The voltage value on the secondary side of the transformers was 100/root(3) V (a phase voltage). Field 3a of the switchboard supplies the rolling mill motor, whose operation causes voltage fluctuations. The scheme of the switchgear with the measuring point marked is shown in Figure 1. The measurement lasted five hours from 11:10 to 16:10. After the initial rolling period (until 11:30), there was a break in the rolling mill operation until about 14:20.

Measurements were performed using a measurement system that allows simultaneous measurement of three phase-to-phase or two-phase voltages. In the hardware part of the measuring system (Figure 2), the signal is first pre-conditioned. The analog signal processing consists of matching the level of the measured signal to the inputs of the optoisolation amplifier, which ensures the separation of the high voltage signal. Then low-pass filtration through a set of anti-aliasing filters is carried out. The formation of the output digital signal from the analog signal takes place in the A/D converter with a 16-bit resolution and a sampling rate of up to 20 kS/s.

The sampling frequency is equal to 20 000 Hz and is inserted in the first row of the attached files.

Ilustracja publikacji

Figure 1. The scheme of the switchgear with the measuring point marked

Ilustracja publikacji

Figure 2. The hardware part of the measurement system

Plik z danymi badawczymi

steel mill.zip
184.6 MB, S3 ETag f926a8f754d637e34aeab8970a936680-1, pobrań: 18
Hash pliku liczony jest ze wzoru
hexmd5(md5(part1)+md5(part2)+...)-{parts_count} gdzie pojedyncza część pliku jest wielkości 512 MB

Przykładowy skrypt do wyliczenia:
https://github.com/antespi/s3md5
pobierz plik steel mill.zip

Informacje szczegółowe o pliku

Licencja:
Creative Commons: by 4.0 otwiera się w nowej karcie
CC BY
Uznanie autorstwa
Dane surowe:
Dane zawarte w datasecie nie zostały w żaden sposób przetworzone.

Informacje szczegółowe

Rok publikacji:
2020
Data zatwierdzenia:
2020-12-17
Data wytworzenia:
2000
Język danych badawczych:
angielski
Dyscypliny:
  • Automatyka, elektronika i elektrotechnika (Dziedzina nauk inżynieryjno-technicznych)
DOI:
Identyfikator DOI 10.34808/wv44-3z34 otwiera się w nowej karcie
Seria:
Weryfikacja:
Politechnika Gdańska

Słowa kluczowe

Powiązane zasoby

Cytuj jako

wyświetlono 134 razy