Problems of Selecting Protection for Shunt Reactors Working in Extra-High Voltage Grids
PublikacjaThis paper presents difficulties encountered when designing protection devices for shunt reactors connected directly to extra-high voltage grids. Using the example of the 400 kV Ełk Bis substation, it has been demonstrated that protection of a shunt reactor based on equipment using measurements of electrical signals from voltage and current transformers has its limitations and, in some cases, may be insufficient.
-
Case studies of resonance phenomena in high voltage overhead power lines with shunt reactors
PublikacjaMisguided design of the towers of power transmission lines can lead to serious problems such as voltage asymmetry, overvoltages, electric arc extinction difficulties or resonance – in case of double circuit line with shunt reactors. The paper points out those threats on example of 400 kV double circuit overhead transmission line with shunt reactors.
-
Protection of Earthing Reactor Connected to the Star Point of a High Voltage Shunt Reactor
PublikacjaThe article presents the problem of protection of earthing reactors connected to the star point of shunt reactors in high voltage lines, with particular regard to the detection of internal faults. Model analyses for an actual system commissioned in 2015, which is intended to be provided with earthing reactors, are included.
-
Neutral earthing reactor protection
PublikacjaThe IEEE and CIGRE recommend protection systems for high voltage shunt reactors. Unfortunately the recommendations do not include guidelines for the protection of neutral earthing reactors, which are often connected to shunt reactors to increase the effectiveness of single pole auto-reclosing. The paper discusses earthing reactor protection issues with particular emphasis on the detection of internal faults. An analysis carried...
-
The Issues of Reactive Power Compensation in High-voltage Transmission Lines
PublikacjaThis paper discusses the selection of compensation shunt reactors for a double-circuit 400 kV transmission line using the example of the newly built Elk Bis – Alytus transmission line. The analysis takes into account various conditions of the power system. The published results relate to voltage levels in steady states and during switching processes and short circuits.
-
Resonance problems in UHV transmission lines
PublikacjaThe paper presents resonance phenomena observed in 400 kV transmission lines in the Polish power system. Two events are analysed, when shunt reactors used for reactive power compensation, caused overvoltages and overcurrent protection tripping as a result of resonance. An oscillographic fault recordings from protection devices are compared to time domain simulation results. The obtained simulation results match fault recordings,...
-
EHV transmission lines wires location on line operation issues - case studies
PublikacjaTransmission lines towers construction affects the line parameters and influences on its operation in the future. Misguided design of the tower can lead to serious problems such as overvoltages, electric arc extinction difficulties, voltage asymmetry, resonance phenomena or increasing of magnetic field near the line. The paper points out those threats on example of 400 kV double circuit overhead transmission line with shunt reactors....
-
Secondary arc modelling for single pole reclosing analyses
PublikacjaThe paper discusses two evaluation methods of single pole auto-reclosing process effectiveness in HV transmission lines. Secondary arc current and recovery voltage calculation results obtained by load flow calculation are compared to the results obtained by the time domain simulations. Moreover, a nonlinear secondary arc model implementation is presented. The paper presents the study results for the three types of EHV transmission...
-
Nonlinear secondary arc model use for evaluation of single pole auto-reclosing effectiveness
PublikacjaPurpose – The purpose of this paper is to discuss two evaluation methods of single pole autoreclosing process effectiveness in HV transmission lines. Secondary arc current and recovery voltage results obtained by load flow calculation are compared to the results obtained by the time domain simulations. Moreover, a nonlinear secondary arc implementation is presented. Design/methodology/approach – A computer simulation studies were...