Abstrakt
Currently, almost all medium voltage cable lines (MV) operate with the return wires earthed at both ends of the cable. Such a way of operation causes that during normal states of operation as well as during disturbances, e.g. short-circuits, in the return wires induce currents whose values mainly depend on the currents flowing in the phase wires. These currents in normal operating states are a source of additional energy losses incurred in the MV cables. The effect can be decreased by the return wires cross-bonding or the phase wires transposition. The paper discusses the potential effects that can be achieved by use of the return wires cross-bonding or the phase wires transposition in the domestic grids.
Cytowania
-
0
CrossRef
-
0
Web of Science
-
0
Scopus
Autorzy (6)
Cytuj jako
Pełna treść
- Wersja publikacji
- Accepted albo Published Version
- DOI:
- Cyfrowy identyfikator dokumentu elektronicznego (otwiera się w nowej karcie) 10.12736/issn.2330-3022.2019204
- Licencja
- otwiera się w nowej karcie
Słowa kluczowe
Informacje szczegółowe
- Kategoria:
- Publikacja w czasopiśmie
- Typ:
- artykuły w czasopismach
- Opublikowano w:
-
Acta Energetica
nr 2,
strony 47 - 53,
ISSN: 2300-3022 - Język:
- angielski
- Rok wydania:
- 2019
- Opis bibliograficzny:
- Dobrzyński K., Lubośny Z., Klucznik J., Falkowski D., Grala J., Noske S.: Cross-Bonding of MV Cable Lines for Energy Losses Decrease// Acta Energetica -Vol. 2,iss. 39 (2019), s.47-53
- DOI:
- Cyfrowy identyfikator dokumentu elektronicznego (otwiera się w nowej karcie) 10.12736/issn.2330-3022.2019204
- Weryfikacja:
- Politechnika Gdańska
wyświetlono 170 razy