Analysis of Induced Voltages and Power Losses in High Voltage Power Cables for Selected Methods of Cables Sheaths Bonding
PublicationPower is increasingly supplied to city centres with 110 kV cable lines. This is a convenient way to supply power, and practically the only one possible in areas of dense urban development. A high-voltage cable contains a coaxial metallic sheath, in which in normal operation and in fault conditions (during short-circuits) significant line-to-earth voltages can be induced, which threatens electric shock and/or damage to the cable’s...
-
Induced sheath voltages in 110 kV power cables – case study
PublicationThis paper considers electric shock hazard due to induced sheath voltages in 110 kV power cables. The purpose of this paper is to find an optimal configuration of the power cable system, taking into account electric shock hazard and ability of the system to transfer maximal power. A computer simulations on a computer model of the local power system, comprising high voltage power cables, were carried out. This model enables to analyse...
-
Induced Sheath Voltages In 110 Kv Power Cables – Case Study
PublicationThe paper considers shock hazard due to induced sheath voltages in 110 kV power cables. Various configurations of the metallic sheaths bonding and earthing (single-point bonding, both-ends bonding, cross-bonding) are analysed. Taking into account shock hazard and ability of the system to power transfer an optimal configuration is proposed.
-
The effect of cable duct diameter on the ampacity of high-voltage power cables
PublicationThe ampacity of power cables depends, among others, on the conditions of heat dissipation from the cable to the environment. Cables are usually laid directly in the ground, but in some sections, they may be placed in ducts, which adversely affects the ampacity of the cable line. The paper presents heat transfer phenomena for cables installed in pipe-type ducts filled with air. The effect of cable duct diameter on this ampacity...
-
Risk of power cables insulation failure due to the thermal effect of solar radiation
PublicationLow-voltage, as well as high-voltage power cable lines, are usually buried in the ground. The ampacity of the power cables in the ground mainly depends on the thermal resistivity of the soil, which may vary in a wide range. A common practice in power cable systems performance is to supply them from a pole of an overhead line. If so, a section of the line is located in free air and can be directly exposed to solar radiation. In...
-
Impact of configuration of earth continuity conductor on induced sheath voltages in power cables
PublicationIn high voltage power cable systems a problem of induced sheath voltages exist. Due to these voltages electric shock and damage of non-metallic outer sheath of the cables may occur. Exposure to voltage of the outer sheath may be very high in case of earth fault with high value of earth current. In order to reduce induced sheath voltages an earth continuity conductor (conductors) along power cables is applied. Configuration of this...
-
Effect of soil moisture on current-carrying capacity of low-voltage power cables
PublicationOne of the factors affecting current-carrying capacity of underground power cables is the thermal resistivity of soil. Its value in the close proximity of the cable is the most important, and for this reason, in some cases, the local soil is replaced with an another soil type or with a cement-sand mixture. The thermal resistivity of the soil is strongly affected by moisture, and in the case of a cement-sand mixture – as tested...
-
Optimization of thermal backfill configurations for desired high-voltage power cables ampacity
PublicationThe ampacity of high-voltage power cables depends, among others, on their core cross-sectional area as well as thermal resistivity of the thermal backfill surrounding the cables. The cross-sectional area of the power cables’ core is selected according to the expected power to be transferred via the cable system. Usually, the higher the power transfer required, the higher the cross-sectional area of the core. However, the cost of...
-
CFD-based evaluation of current-carrying capacity of power cables installed in free air
PublicationEvaluation of current-carrying capacity of power cables and selection of cross-sectional area of their conductors are mainly performed in accordance with requirements of EN, IEC or IEEE standards. However, these standards do not provide all methods of cables installation and location which occur in practice. Thus, in some cases, performance of advanced modeling of various thermal phenomena, affecting power cables current-carrying...
-
Impact of thermal backfill parameters on current-carrying capacity of power cables installed in the ground
PublicationProper design of power installations with the participation of power cables buried in homogeneous and thermally well-conductive ground does not constitute a major problem. The situation changes when the ground is non-homogeneous and thermally low-conductive. In such a situation, a thermal backfill near the cables is commonly used. The optimization of thermal backfill parameters to achieve the highest possible current-carrying capacity...
-
Electrical Tree Growth Behavior Under AC and DC High Voltage in Power Cables
PublicationThis work investigates the impact of an applied AC and DC high voltage on the electrical tree behavior in extruded cross-linked polyethylene (XLPE) insulation based on simulation and experimental validation. Extensive partial discharge (PD) testing methods are being implemented for high voltage cables under AC voltage for monitoring their condition. However, these PD testing methods cannot be utilized for power cables under DC...
-
Ampacity of power cables exposed to solar radiation – recommendations of standards vs. CFD simulations
PublicationThe aim of the paper is to evaluate the ampacity of a low-voltage single power cable according to: 1) recommendations of the standard IEC 60287, 2) a Computational Fluid Dynamics method, implemented in Ansys software; and comparison of the results obtained for these two cases. Moreover, limitations of recommendations of the above mentioned standard are indicated.
-
Safety issues referred to induced sheath voltages in high-voltage power cables – case study
PublicationLoad currents and short-circuit currents in high-voltage power cable lines are sources of the induced voltages in the power cables’ concentric metallic sheaths. When power cables operate with single-point bonding, which is the simplest bonding arrangement, these induced voltages may introduce an electric shock hazard or may lead to damage of the cables’ outer non-metallic sheaths at the unearthed end of the power cable line. To...
-
Effect of solar radiation on current-carrying capacity of PVC-insulated power cables – the numerical point of view
PublicationPower cables are usually buried in the soil, which results in their relatively high current-carrying capacity. However, there are cases in which the starting/final section of a cable line runs along a pole of an overhead power line. Power cables can be directly exposed to solar radiation then, and this negatively influences their current-carrying capacity as well as estimated life of the cables’ insulation. An analysis of thermal...
-
Calculation of Induced Sheath Voltages in Power Cables – Single Circuit System versus Double Circuit System
PublicationThis paper presents comparison of values of induced sheath voltages in power cable metallic sheaths when one or two cables per phase are used. Calculation of voltages is performed for various phase sequences of the power cables. Three types of the sheaths bonding and earthing are considered. Shock hazard and voltage stress of non-metallic outer sheath of cables are evaluated. The proposed, optimal configuration of the power cable...
-
Problems of Connecting Wind Farms to the Power System with HV Cables
PublicationThis paper presents problems caused by connecting wind farms to a power system with high voltage cables. The author highlights possible problems with reactive power compensation, depending on the arrangement of the shunt reactor connection and settings of control systems for reactive power and voltage of the wind farm. The paper also discusses issues of increasing active power losses caused by a shunt reactor installation.
-
The Impact of Thermal Stresses on Volume Resistivity: Performance Comparison between TR-XLPE and XLPE Cables
PublicationMost failures in electric power cables are attributed to the development of water trees inside the insulating materials. Thus, the development and utilization of Tree Retardant Cross-Linked Polyethylene (TR-XLPE) based cables have recently been given great attention to overcome the treeing issues. TR-XLPE cables use low-density polyethylene compounds suppressing the formation of water trees while retaining excellent electrical,...
-
Inception and Propagation of Electrical Trees in the Presence of Space Charge in HVAC Extruded Cables
PublicationThis paper presents the space charge impact on the inception and propagation of electrical trees in cross-linked polyethylene (XLPE) insulation via simulations and experimentation. A 3D finite element analysis (FEA)-based modeling is proposed to simulate electrical trees via a needle embedded on the XLPE insulation. The proposed FEA model demonstrates the influence of the space charge magnitude and polarity on the initiation of...
-
Design of power cable lines partially exposed to direct solar radiation – special aspects
PublicationPower cable lines are usually buried in the ground. However, in some cases, their ending sections are mounted along the supports of overhead lines. This leads to a situation where the cables are exposed to direct solar radiation and, consequentially, overheat. The paper presents the advanced computer modelling of power cables’ heating, considering their insolation as well as the effect of wind. The temperature and current-carrying...
-
Computer-aided Analysis of Induced Sheath Voltages in High Voltage Power Cable System
PublicationThis paper concerns the effect of configuration of high voltage power cables on induced voltages in their metallic sheaths. One, two or three cables per phase and phase sequence of the cables are considered. Computing of the voltages was performed for a normal operation and in case of earth fault. Various ways of the sheaths bonding are considered as well. Shock hazard and voltage stress of non-metallic outer sheath of cables are...
-
Overheating of underground power cable line due to its partial exposition to solar radiation
PublicationCurrent-carrying capacity of underground power cable lines depends, among others, on thermal resistivity of the soil and cables layout: trefoil formation, flat formation with or without spacing. If conditions for heat transfer in the ground are favorable, the current-carrying capacity is relatively high. Therefore, it generates risk of the power cables overheating, if part of the cable line is located vertically in the air, to...
-
Study of Soil Temperature and Moisture Changes in a Physical Model of an Underground Cable Line
PublicationThe ampacity of power cables is highly dependent on the thermal resistivity of the soil in which they are laid. The lower it is, the higher this ampacity. The thermal resistivity of the soil decreases as its moisture increases. Therefore, it is preferable that the soil around the cables has high moisture. Unfortunately, the heat generated in heavily loaded cables causes the migration of moisture from the surrounding soil, which...
-
Position Estimation in Corridors Along the Coupled Mode of Radiating Cables
PublicationRadiating cables are mostly used to provide radio communication in tunnels or corridors, but they can also be used to estimate the position of a mobile terminal along the cable. In this paper, a measuring receiver’s position was estimated by measuring the difference in the direct signal’s reception time, which was generated by a transmitter connected to one end of the radiating cable, and the delayed signal retransmitted from another...
-
Simple model of rain wind induced vibrations of stayed cables.
PublicationAnalizowano prosty, liniowy model drgań kabli mostów wantowych pod obciążeniem wiatrem i deszczem. Zakłada się, iż częstotliwość ruchu górnej kropli po powierzchni kabla i częstotliwość kabla są równe oraz iż amplituda ruchu kropli dla danej prędkości wiatru są stałe. Otrzymane rezultaty są porównane z istniejącymi w literaturze wynikami badań eksperymentalnych. Podaje się analityczne związki służące do oszacowania tłumienia...
-
Evaluation of fire hazard in electrical installations due to unfavorable ambient thermal conditions
PublicationEvaluation of fire hazard caused by electrical installations is a difficult and important topic, and it limits the possibility of loss of life or health of people, as well as the occurrence of significant property damage. In particular, this hazard was caused by power cables and especially photovoltaic (PV) installations. The authors proved that power cables directly exposed to strong solar radiation are likely to exceed maximum...
-
The Effect of Protrusions on the Initiation of Partial Discharges in XLPE High Voltage Cables
PublicationThis paper is focusing on 3D Finite Elements Analysis (FEA) based modelling of protrusions as defects or imperfections in the XLPE high voltage cable. This study is aiming to examine the impact protrusions have on the initiation of partial discharges. Spherical and ellipsoidal protrusions with different sizes at the conductor screen of the high voltage cable is an essential content of this paper. In addition, a spherical gas-filled...
-
Application of Structural Control Systems for the Cables of Cable-Stayed Bridges: State-of-the-Art and State-of-the-Practice
PublicationStay cables are one of the key elements of cable-stayed bridges and are characterized by lightweight, low inherent damping, and high flexibility. They are continuously subjected to small-to large-amplitude vibrations due to various types of dynamic loads that may, in the long term, cause fatigue and fracture problems for the cable system, and may eventually compromise the safety of cable-stayed bridges. Thus, several countermeasures...
-
Experiment-Based Study of Heat Dissipation from the Power Cable in a Casing Pipe
PublicationThe paper deals with the important challenges in terms of electricity transmission by means of underground cable lines. The power cable’s performance is characterized by an ampacity that represents its maximum electric current-carrying capacity. The ampacity of power cables depends on their ability to diffuse the heat generated by the current flow into the environment. In the performed research, the analysis of the efficiency of...
-
Modelling of MV and HV Cable Lines
PublicationOverhead and cable lines are fundamental elements of power systems. Participation of cable lines is smaller and their percentage decreases as voltage is increased. HV cable lines are often built with the use of cables which are composed of coaxial metallic sheaths. Such cables are also often used in MV networks. The sheath may operate in different confgurations. In the case of Polish MV network the sheaths are earthed at both ends....
-
Energy losses reduction in the medium voltage cable line – case study
PublicationThe paper presents an analysis of energy losses in a power cable system, which is composed of two 30 kV cable lines. This cable system is located at the seaside holiday area, so the load profile during a year is specific. Energy losses related to reactive power transmission, as well as to currents induced in the sheaths of the cables, are subject to analysis. Measurements were made in the system in order to prepare a computer model...
-
Możliwości sterowania mocą bierną elektrowni wiatrowej : Reactive power control methods in wind parks
PublicationReferat poświęcony jest zagadnieniu sterowania mocą bierną w elektrowniach wiatrowych. W pierwszej części referatu opisano tło problemu sterowania mocą bierną w parkach wiatrowych, podano powody, dla których moc bierna powinna podlegać regulacji oraz zarysowano metody, które mogą być do niej użyte. W celu sprawdzenia proponowanych metod kompensacji, zbudowano model matematyczny elektrowni wiatrowej, którego poszczególne elementy...
-
The conducted immunity test of a power supply unit in accordance with EMC standards
Open Research DataThe dataset presents a result of measurements that are a part of immunity tests to conducted disturbances, induced by radio-frequency fields. The immunity tests were carried out on the mains cable of the DF1723003TC NDN power supply. Tests of immunity of electronic systems to conducted disturbances in the frequency range from 150 kHz to 230 MHz are...
-
Problemy przyłączania farm wiatrowych do systemu elektroenergetycznego z wykorzystaniem kabli WN
PublicationArtykuł prezentuje problemy, jakie rodzi przyłączanie farm wiatrowych do systemu elektroenergetycznego za pomocą kabli wysokiego napięcia. Autor wskazuje możliwe problemy z kompensacją mocy biernej, w zależności od sposobu przyłączenia dławika kompensacyjnego i nastawień układów regulacji mocy biernej oraz napięcia farmy wiatrowej. Artykuł porusza też zagadnienia zwiększenia strat mocy czynnej powodowanych instalacją dławików kompensacyjnych.
-
Zastosowanie specjalnego uziemienia żył powrotnych w liniach kablowych SN
PublicationW artykule porównano metody uziemiania żył powrotnych kabli średniego napięcia. Głównym kryterium oceny poszczególnych rozwiązań było ograniczenie strat w przesyle energii elektrycznej oraz zapewnienie ochrony przeciwprzepięciowej osłon kabli. Na podstawie symulacji kabli zamodelowanych w programie CYMCAP i otrzymanych wyników obciążalności prądowej i strat w linii zaprezentowano metodę krzyżowania żył powrotnych (CB – cross-bonding...
-
The conducted immunity test of a power supply unit in the frequency range from 19 MHz to 26 MHz for the RF voltage level of 3 V
Open Research DataThe dataset presents a result of measurements that are a part of immunity tests to conducted disturbances, induced by radio-frequency fields. The immunity tests were carried out on the mains cable of the DF1723003TC NDN power supply unit. Tests of immunity of electronic systems to conducted disturbances in the frequency range from 19 MHz to 26 MHz were...
-
The conducted immunity test of a power supply unit in the frequency range from 19 MHz to 26 MHz for the RF voltage level of 1 V
Open Research DataThe dataset presents a result of measurements that are a part of immunity tests to conducted disturbances, induced by radio-frequency fields. The immunity tests were carried out on the mains cable of the DF1723003TC NDN power supply unit. Tests of immunity of electronic systems to conducted disturbances in the frequency range from 19 MHz to 26 MHz were...
-
The conducted immunity test of a power supply unit in the frequency range from 19 MHz to 26 MHz for the RF voltage level of 10 V
Open Research DataThe dataset presents a result of measurements that are a part of immunity tests to conducted disturbances, induced by radio-frequency fields. The immunity tests were carried out on the mains cable of the DF1723003TC NDN power supply unit. Tests of immunity of electronic systems to conducted disturbances in the frequency range from 19 MHz to 26 MHz were...
-
Quality Evaluation of Voice Transmission Using BPL Communication System in MV Mine Cable Network
PublicationThis article presents results of a quality evaluation study, considering voice transmission in a 6 kV medium voltage cable network using the BPL (Broadband over Power Line) communication system. The tests are carried out under real mining conditions for the selected power cable without voltage, earthed at both sides. Such a method of monitoring work conditions is of great importance, especially during a disaster. Power cables are...
-
Incomplete Cross-Bonding in the MV Line. Experience from the Operation of MV Single Cable Lines
PublicationCable lines are one of the basic components of power systems. Medium and high voltage cables mainly comprise a metallic sheath, which is concentric to the main core conductor. There are several operating schemes of such cable lines, which differ in the place of earthing of sheaths and the possible use of the sheaths and/or conductors crossing. The sheaths cross-bonding is typically done in two places of one cable line section,...
-
Modeling and Evaluation of Electric Treeing Phenomena in Polymeric Cable Insulation
PublicationThis paper investigates the treeing phenomenon in polymeric materials such as crosslinked polyethylene (XLPE) that is widely used in medium and high voltage power cables as primary insulation. The modeling of electrical tree growth in the insulation from its initiation to breakdown is significant research work that illustrates the discharge dynamics and its impact on aging process in polymeric insulation. This study utilizes pulse...
-
The conducted immunity test of an AC adaptor in accordance with EMC standards
Open Research DataThe dataset presents a result of measurements that are a part of immunity tests to conducted disturbances, induced by radio-frequency fields. The immunity tests were carried out on the mains cable of the ac adaptor PHILIPS DC power supply SBC 6654. Tests of immunity of electronic systems to conducted disturbances in the frequency range from 150 kHz...
-
BPL-PLC Voice Communication System for the Oil and Mining Industry
PublicationApplication of a high-efficiency voice communication systems based on broadband over power line-power line communication (BPL-PLC) technology in medium voltage networks, including hazardous areas (like the oil and mining industry), as a redundant mean of wired communication (apart from traditional fiber optics and electrical wires) can be beneficial. Due to the possibility of utilizing existing electrical infrastructure, it can...
-
Ultra-Wideband Vivaldi Antenna with an Integrated Noise-Rejecting Parasitic Notch Filter for Online Partial Discharge Detection
PublicationPower transformers and gas-insulated switchgear (GIS) play crucial roles in electrical power grids. However, they may suffer from degradation of insulation material due to wear and tear, leading to their imminent failure. Partial discharges (PDs) are an initial sign of insulation materials degradation which emit signals spanning various physical domains, including electromagnetic. PDs are temporally narrow, high-frequency, stochastic...
-
Experimental Study of the Influence of Noise Level on the Uncertainty Value in a Measurement System Containing an Analog-to-Digital Converter
Open Research DataFor newly developed measuring systems it is easy to estimate type B uncertainties based on the technical data of the measuring modules applied. However, it is difficult to estimate A type un-certainties due to the unknown type and level of interferences infiltrating into the measuring sys-tem. This is a particularly important problem for measurements...
-
Place attachment, place identity, and visual pollution sensitivity.
Open Research DataThe data include individual responses on the following scales (1) place attachment, (2) place identity, and (3) visual pollution sensitivity. Each line represents responses obtained from one participant and his or her demographic characteristics. like gender, age, and education level.
-
Analysis of passenger car crash with a cable barrier installed with anti-glare screens on a horizontal convex road curve with 400 m radius
PublicationHigh-tension cable barriers have been used on roads for a relatively short period compared with other types of road barriers. Hence, there remains a need for further research on various crash scenarios. An important issue is the performance of a cable barrier on a road curve, particularly when a vehicle impacts the convex side of the barrier. To address this issue, the analysis in this study considers a system of anti-glare screens...
-
Identyfikacja parametrów dynamicznych want mostu Rędzińskiego we Wrocławiu
Publicationthe paper presents results of dynamic analysis conducted on stay-cables of rędziński bridge in wrocław. identified in situ dynamic parameters (natural frequency and logarithmic decrement damping ratio) of selected stays were and compared to the values featured in the project.
-
AC loss measurements in superconducting magnet
PublicationThis report contains ordered theoretical informations about AC loss in superconducting magnets and cables. A software program to evaluate data from AC loss measurements with V-I method was made and it is also described. Examples of measurement data and result data are shown here.
-
The Selection of Anchoring System for Floating Houses by Means of AHP Method
PublicationThis paper indicates and analyses the use of anchoring systems, such as mooring piles, booms, mooring cables, and deadweight anchors with additional elastic connectors, which are the most frequently applied by the producers of floating houses. The selection of the most advantageous anchoring system is complicated and requires the application of quantitative and qualitative data and methods. This publication presents the results...
-
Shape and force control of cable structures with minimal actuators and actuation
PublicationShape adjustment and stress control can be considered as one of the effective parameters in prestressed cable structures since such structures are widely constructed nowadays due to their characteristics. The assembly errors and applied loads hugely affect the cables’ nodal positions and stress due to their delicacy. The former could disturb the shape, which affects the appearance and the function of the structure. In contrast,...