Fault Loop Impedance Measurement in Circuits Fed by UPS and Principle of Safety Protection
PublikacjaThis paper indicates a significant problem of uncertainty of fault loop impedance (FLI) measurement in circuits powered from uninterruptible power supply (UPS) (double-conversion AC-DC-AC). The correctly determined value of this impedance, related to the short-circuit current disconnection time and to the reference value, is one of the most important elements that determines the approval of an electrical installation and its receivers...
-
A method of earth fault loop impedance measurement without unwanted tripping of RCDs
PublikacjaIn low-voltage networks, earth fault loop impedance (EFLI) measurement is the basis for assessing the effectiveness of automatic disconnection of supply. Such a measurement is performed during initial and periodical verification, especially in a TN low-voltage network. Nowadays, due to widespread application of residual current devices (RCDs), such test is difficult in many circuits because RCDs operate during the test. In this...
-
Measurement of the earth fault loop impedance in a low voltage network with operating loads
PublikacjaW artykule przedstawiono problematykę dokładności pomiaru impedancji pętli zwarciowej w sieciach z obciążeniami roboczymi. Klasyczne metody pomiarowe i mierniki mogą powodować błędy pomiaru przekraczające dopuszczalną wartość. Z tego powodu może wystąpić ryzyko porażenia prądem elektrycznym, ponieważ przy doziemieniu nie będzie spełniony warunek samoczynnego wyłączenia zasilania. Błędy pomiaru w sieci z obciążeniami roboczymi można...
-
Fault loop impedance measurement in low voltage network with residual current devices
PublikacjaW sieciach i instalacjach niskiego napięcia z wyłącznikami różnicowoprądowymi pomiar impedancji pętli zwarciowej jest kłopotliwy. Prąd pomiarowy powoduje ich zbędne zadziałanie, co uniemożliwia prawidłowe wykonanie pomiaru. W artykule omówiono przyczyny zbędnego zadziałania wyłączników różnicowoprądowych podczas pomiaru impedancji pętli zwarciowej oraz warunki, w jakich ten pomiar można wykonać poprawnie.
-
Selected problems of earth fault loop impedance testing in circuits fed from UPS
PublikacjaIn the paper a principle of earth fault loop impedance testing in low voltage systems has been presented. Selected factors, influencing accuracy of the testing, are indicated. A structure of UPS of VFI-type and the problem of impedance testing in circuits with such type of UPS are discussed.
-
Evaluation of applicability of classic methods of a fault loop impedance measurement to circuits with residual current devices
PublikacjaMeasurement of fault loop impedance in low voltage grids and systems is in most cases performed to verify the effectiveness of protection against electric shock by automatic disconnection of supply. For the sake of measurement accuracy, it is advisable to perform it using large current. Unfortunately, in circuits with residual current devices which are very widely used nowadays, a large measurement current may trigger those devices...
-
Method of earth fault loop impedance measurement without nuisance tripping of RCDs in 3-phase low-voltage circuits
PublikacjaVerification of electrical safety in low-voltage power systems includes the measurement of earth fault loop impedance. This measurement is performed to verify the effectiveness of protection against indirect contact. The widespread classic methods and meters use a relatively high value of the measuring current (5–20) A, so that they are a source of nuisance tripping of residual current devices (RCDs). The meters dedicated to circuits...
-
Transient States during Short-circuit in a Line Powered by UPS and its Impact on Earth Fault Loop Impedance Measurement and Power Quality
PublikacjaThe short-circuit in a line powered by Uninterruptible Power Supply (UPS) during different UPS operation modes is presented in the article. The transient state condition related to the short-circuit in a line fed from double conversion On-line UPS is discussed in detail. The results of the measurements of earth fault loop impedance (FLI) in circuits powered by UPS with the instruments of various manufacturers are presented. The...
-
Uncertainty estimation of loop impedance measurement determined by the vector method
PublikacjaThis article presents a detailed analysis of uncertainty estimation of loop impedance measurement determined by the vector method. The analysis includes the following estimates: resistance variance, voltage variance and time measurement variance. This paper presents a methodology for estimating the combined standard uncertainty of loop impedance by the vector method. The vector method allows to determine loop impedance based on...
-
A new method of fault loop resistance measurement in low voltage systems with residual current devices
PublikacjaThis paper presents a new method of fault loop resistance measurement in low voltage systems with residual current devices. The method enables measuring fault loop resistance without nuisance tripping of residual current devices, by application an unconventional waveform of measurement current. It is important for proper verification of the effectiveness of protection against electric shock.
-
Fault Diagnostics in PEMFC Stacks by Evaluation of Local Performance and Cell Impedance Analysis
PublikacjaStarvation, flooding, and dry‐out phenomena occur in polymer electrolyte membrane fuel cells (PEMFCs), due to heterogeneous local conditions, material inhomogeneity, and uneven flow distribution across the single cell active area and in between the individual cells. The impact of the load level and air feed conditions on the performance was identified for individual single cells within a 10‐cell stack. Analysis of the current density...
-
STANY NIEUSTALONE TOWARZYSZĄCE POMIAROWI IMPEDANCJI PĘTLI ZWARCIA W OBWODACH WYJŚCIOWYCH ZASILACZY BEZPRZERWOWYCH UPS
PublikacjaW pracy przedstawiono metodykę i wyniki pomiarów stanów nieustalonych w zasilaczu bezprzerwowym (UPS) typu on - line. Do rejestracji zdarzeń po stronie zasilania i na wyjściu UPS wykorzystano dwa przyrządy do pomiaru jakości energii elektrycznej zsynchronizowane czasowo. Rejestratory kompresują uzyskane dane pomiarowe, co może wprowadzać dodatkowe błędy pomiaru wielkości mierzonych – napięć i prądów. Dodatkowe rejestracje oscyloskopem...
-
Effect of the let-through energy of overcurrent protective devices on the temperature of conductors during short-circuits
PublikacjaThe scope of the verification of low-voltage systems covers the earth fault loop impedance measurement. This measurement is usually performed with the use of low-value current meters, which force a current many times lower than the one occurring during a real short-circuit. Therefore, the international standard recommends consideration of the increase of resistance of conductors with the increase of temperature, which may occur...
-
Verification of safety in low-voltage power systems without nuisance tripping of residual current devices
PublikacjaLow-voltage power systems require initial and periodical verification to check the effectiveness of protection against electric shock. As a protection in case of fault, automatic disconnection of supply is most often used. To verify such a protection measure, the earth fault loop impedance or resistance is measured. This measurement is easy to perform in circuits without residual current devices. When residual current devices are...
-
Residual Current Devices: Selection, Operation, and Testing
PublikacjaIn this book, the idea for residual current protection has been presented. The evolution in construction types of residual current devices, which has taken place over decades, is discussed. Types and functional properties of the contemporary residual current devices are described. The main parameters of these devices, from the point of view of their selection and application, are indicated. Special constructions of the protective...
-
Badanie wybranych właściwości wyłączników różnicowoprądowych typu F
PublikacjaW instalacjach elektrycznych niskiego napięcia instaluje się coraz więcej przekształtników energoelektronicznych (systemy fotowoltaiczne, instalacje ładowania pojazdów elektrycznych, układy napędowe o regulowanej prędkości obrotowej silnika), a mają one wpływ na dobór typu wyzwalania wyłączników różnicowoprądowych (AC, A, F lub B). W obwodach, w których pojawia się prąd różnicowy zawierający składowe o częstotliwości innej niż...
-
Broken Rotor Symptons in the Sensorless Control of Induction Machine
PublikacjaInverter fed sensorless controlled variable speed drives with induction machine are widely used in the industry applications, also in wind power generation and electric vehicles. On-line self diagnostic systems implementation is needed for early stage fault detection and avoiding a critical fault. Diagnostic algorithms in modern DSP-based controllers can operate simultaneously with control system functions. In the closed-loop controlled...
-
State and control system variables sensitivity to rotor asymmetry in the induction motor drive
PublikacjaThe aim of this paper is to undertake analysis and comparison of the closed-loop and sensorless control systems sensitivity to the broken rotor for diagnostic purposes. For the same vector control system induction motor drive analysis concerning operation with the asymmetric motor, broken rotor fault handling and operation were investigated. Reliability, range of stable operation, fault symptoms and application of diagnosis methods...
-
Experimental verification of a new method of loop resistance testing in low voltage systems with residual current devices
PublikacjaA periodical verification of the effectiveness of protection against electric shock shall be performed in low voltage systems. The scope of this verification includes loop impedance/resistance testing. If a residual current device is installed in a tested circuit, this testing is problematic. A residual current device trips out during the test, because of the high value of measurement current. This precludes the execution of the...
-
Investigation of the electrochemical behaviour of AA1050 aluminium alloy in aqueous alkaline solutions using Dynamic Electrochemical Impedance Spectroscopy
PublikacjaThe paper presents the electrochemical behaviour of aluminium alloy AA1050 in aqueous alkaline media in the pH range 14–8.5. Electrochemical study was applied in order to obtain comprehensive information on the mechanism and kinetics of the process of anodic dissolution of aluminium, supplemented by monitoring of surface topography using an electron microscope. The corrosion rate of AA1050 increases with increasing concentration...
-
Broken rotor bar impact on sensorless control of induction machine
PublikacjaThe aim of the research is analysis of the sensorless control system of induction machine with broken rotor for diagnostic purposes. Increasing popularity of sensorless controlled variable speed drives requires research in area of reliability, range of stable operation, fault symptoms and application of diagnosis methods. T transformation (Cunha et al.,2003) used for conversion of instantaneous rotor currents electrical circuit...
-
Determination of Mathematical Model Parameters of a Medium Frequency Transformer
PublikacjaThe paper presents the results of experimental studies of the medium frequency transformer. The object of the research was a prototype of a single-phase transformer with a core made of ferrite I-core elements and windings made of Litz conductors. The research was carried out to determine the parameters of the transformer's mathematical model. The scope of the tests included determining the magnetic hysteresis loop and measuring...
-
Design and optimization of a novel compact broadband linearly/circularly polarized wide-slot antenna for WLAN and Wi-MAX applications
PublikacjaA novel topologically modified structure of a compact low profile wide-slot antenna for broadband applications is presented. The antenna comprises a modified E-shaped slot with unequal arm lengths in the ground plane, and a parasitic quasi-rectangular loop placed coplanar with the feedline. For exciting orthogonal modes with equal amplitude, a single-point feeding technique with an asymmetrical geometry of the coplanar waveguide...
-
A Simple-Topology Compact Broadband Circularly Polarized Antenna With Unidirectional Radiation Pattern
PublikacjaIn this letter, a geometrically simple, reflector-backed single-point-fed circularly polarized (CP) antenna with unidirectional radiation pattern is presented. The structure comprises a simple coplanar waveguide (CPW) feeding circuit with an open slot etched on one side of the coplanar ground. The enhanced CP bandwidth is obtained by combining the loop mode, the slot mode, and the asymmetrical configuration of the coplanar ground...
-
Zero-Pole Approach in Microwave Passive Circuit Design
PublikacjaIn this thesis, optimization strategies for design of microwave passive structures including filters, couplers, antenna and impedance transformer and construction of various surroogate models utilized to fasten the design proces have been discussed. Direct and hybrid optimization methodologies including space mapping and multilevel algorithms combined with various surrogate models at different levels of fidelity have been utilized...
-
Implementation of spatial/polarization diversity for improved-performance circularly polarized multiple-input-multiple-output ultra-wideband antenna
PublikacjaIn this paper, spatial and polarization diversities are simultaneously implemented in an ultra-wideband (UWB) multiple-input-multiple-output (MIMO) antenna to reduce the correlation between the parallel-placed radiators. The keystone of the antenna is systematically modified coplanar ground planes that enable excitation of circular polarization (CP). To realize one sense of circular polarization as well as ultra-wideband operation,...
-
A Clustering-Based Methodology for Selection of Fault Tolerance Techniques
PublikacjaDevelopment of dependable applications requires selection of appropriate fault tolerance techniques that balance efficiency in fault handling and resulting consequences, such as increased development cost or performance degradation. This paper describes an advisory system that recommends fault tolerance techniques considering specified development and runtime application attributes. In the selection process, we use the K-means...
-
PCA based Fault Tolerant MPC
PublikacjaThis chapter presents a Fault Tolerant - Model Predictive Control (FT-MPC) schemes for sensor faults accommodation. A Fault Detection and Isolation (FDI) Unit, which is an integral part of FT-MPC system, is based on the Principal Component Analysis (PCA) method. Introduced approach enables efficient bias and drift faults accommodation in single, as well as simultaneous faults case. Simple simulation exercise is presented.Rozdział...
-
Faults and Fault Detection Methods in Electric Drives
PublikacjaThe chapter presents a review of faults and fault detection methods in electric drives. Typical faults are presented that arises for the induction motor, which is valued in the industry for its robust construction and cost-effective production. Moreover, a summary is presented of detectable faults in conjunction with the required physical information that allow a detection of specific faults. In order to address faults of a complete...
-
Time-current tripping curves of arc fault detection devices
PublikacjaTripping curves of arc fault detection devices, in accordance with PN-EN 62606 “General requirements for arc fault detection devices” have been presented in the paper. Consequently the most fundamental differences in arc fault detection devices tripping compared to circuit-breakers and residual current devices have been indicated.
-
Mechanical Strength of MV Ship-switchgear During Fault Arc
PublikacjaIn the paper the analysis of pressure stressed in enclosure during fault arc inside switchgear is pre-sented as well. There is introduced the method based on determining stresses which are sum of tensile stresses (membrane) and deflection stresses. For tensile stresses nalysis the energy method, for unrestrainedly supported rectangular plate, was used. In the further part of the paper, the calculations and measurements results...
-
Power Hardware-in-the-Loop Approach In Power System Development
PublikacjaThe main objective of the research is the verification of the Power Hardware-In-The-Loop (PHIL) approach in power system analysis and design. The premise of the article is that using PHIL approach the performance of the power system in steady and transient state conditions can be analysed in real power system conditions. Models of induction machine were developed and real time simulations were performed. Simulation variables were...
-
Possibility of Fault Detection in Sensorless Electric Drives
PublikacjaThe work presents a fault detection method for an induction motor drive system with inverter output filter. This approach make use of a load torque state observer, which complete structure is presented along with the used control structure. Moreover, the demonstrated drive system operates without rotor speed measurement in conjunction with the multiscalar control. The verification of the demonstrated idea was performed on an experimental...
-
Polynomial description of dynamic impedance spectrogram—introduction to a new impedance analysis method
PublikacjaThis paper presents a polynomial description of spectrograms obtained using Dynamic Electrochemical Impedance Spectroscopy. A method to fit the polynomial degree correctly is discussed. A simple electrical system of a diode connected in parallel with a capacitor was used for testing. Dynamic impedance measurements during potentiodynamic polarization were conducted. This paper presents an alternative analysis method that allows...
-
Harmony Search for Self-configuration of Fault–Tolerant and Intelligent Grids
PublikacjaIn this paper, harmony search algorithms have been proposed to self-configuration of fault-tolerant grids for big data processing. Self-configuration of computer grids lies in the fact that new computer nodes are automatically configured by software agents and then integrated into the grid. A base node works due to several configuration parameters that define some aspects of data communications and energy power consumption. We...
-
Polynomial analysis as a new way of describing dynamic impedance spectra – Differential and relative impedance spectra
PublikacjaModel measurements of an equivalent electrical system were carried out using the technique of Dynamic Electrochemical Impedance Spectroscopy. The measurement took the form of potentiodynamic changes imposed on the tested system. Using the possibility of continuous impedance measurements, an attempt was made to develop an original and innovative method of analyzing impedance spectrograms, which is termed polynomial analysis. As...
-
The effect of the motor filters on earth fault current waveform in circuits with variable speed drives
PublikacjaIn circuits with variable speed drives distorted earth fault current flows. Earth fault current distortion influences the threshold of ventricular fibrillation. This paper presents earth fault current distortion in circuits with variable speed drives when motor filter is used. Two types of motor filter are analyzed. For every type of filter the effect of earth fault current distortion on ventricular fibrillation is evaluated.
-
The effect of the motor filters on earth fault current waveform in circuits with variable speed drives
PublikacjaIn circuits with variable speed drives distorted earth fault current flows. Earth fault current distortion influences the threshold of ventricular fibrillation. This paper presents earth fault current distortion in circuits with variable speed drives when motor filter is used. Two types of motor filter are analyzed. For every type of filter the effect of earth fault current distortion on ventricular fibrillation is evaluated.
-
Investigation of the influence of capilary effect on operation of the loop heat pipe
PublikacjaIn the paper presented are studies on the inestigation of the capillary forces effect inducted in the porous structure of a loop heat pipe using water and ethanol ad test fluids. The potential application of such effects is for example in the evaporator of the domestic micro-CHP unit, where the reduction of pumping power could be obtained. Preliminary analysis of the results indicates water as having the best potential for developing...
-
Fast Real-Time RDFT- and GDFT-Based Direct Fault Diagnosis of Induction Motor Drive
PublikacjaThis paper presents the theoretical analysis and experimental verification of a direct fault harmonic identification approach in a converter-fed electric drive for automated diagnosis purposes. On the basis of the analytical model of the proposed real-time direct fault diagnosis, the fault-related harmonic component is calculated using recursive DFT (RDFT) and Goertzel DFT (GDFT), applied instead of the full spectrum calculations...
-
Novel Fault Identification for Electromechanical Systems via Spectral Technique and Electrical Data Processing
PublikacjaIt is proposed, developed, investigated, and validated by experiments and modelling for the first time in worldwide terms new data processing technologies, higher order spectral multiple correlation technologies for fault identification for electromechanical systems via electrical data processing. Investigation of the higher order spectral triple correlation technology via modelling has shown that the proposed data processing technology...
-
The effectivness of fault detection in common rail injectors examination methods
PublikacjaThe article presents the effectiveness tests of fault detection in common rail injectors. 40 injectors with different wear levels were tested. Testing was made on two test benches of a completely different design. Research includes comparison of accuracy, reproducibility and testability to detect specific defects. A device was created for visualization of the fuel injector spraying steam.
-
Loop-mediated isothermal amplification (LAMP) as a diagnostic tool in detection of infectious diseases
PublikacjaLoop-mediated isothermal amplification (LAMP) is a gene amplification method which amplifies DNA with high specificity and efficiency under isothermal conditions. Because of its rapidity and simplicity, it is a valuable diagnostic tool in the early detection and identification of infectious diseases. LAMP method is based on the use of a set of four to six specially designed primers spanning six to eight distinct sequences on the...
-
Closed-loop stimulation of temporal cortex rescues functional networks and improves memory
PublikacjaMemory failures are frustrating and often the result of ineffective encoding. One approach to improving memory outcomes is through direct modulation of brain activity with electrical stimulation. Previous efforts, however, have reported inconsistent effects when using open-loop stimulation and often target the hippocampus and medial temporal lobes. Here we use a closed-loop system to monitor and decode neural activity from direct...
-
Platform Supporting the Esophageal Impedance Analysis
PublikacjaThe esophageal pH-impedance examination is one of the most popular diagnostic methods for identifying the upper gastrointestinal tract’s diseases. Inconclusive test evaluation criteria makes it difficult to state the definite diagnosis. In this paper, the computer platform supporting the research and teaching process in the area of pH-impedance analysis is presented. Users, having a variety of mathematical and statistical methods...
-
Fault diagnosing system of wheeled tractors
PublikacjaA defect of complex wheeled tractor assembles most frequently negative influence on exploitation efficiency, safety and exhaust gases emission. Structure complexity of wheeled tractors requires more and more advanced diagnostic methods for identification of their serviceable possibilities as well in manufacturing step as in exploitation. In classical diagnosing methods of wheeled tractor defects states mapping by measured diagnostic...
-
Using an IEEE1149.1 Test Bus for Fault Diagnosis of Analog Parts of Electronic Embedded Systems
PublikacjaThe new solution of a BIST called the JTAG BIST for self-testing of analog parts of electronic embedded systems is presented in the paper. The JTAG BIST consists of the BCT8244A and SCANSTA476 integrated circuits of Texas Instruments controlled via the IEEE 1149.1 bus. The BCT8244A is a scan test device with octal buffers, and the SCANSTA476 is a 12-bit ADC with 8 analog input channels. Self-testing approach is based on the fault...
-
Improving sensitivity of residual current transformers to high frequency earth fault currents
PublikacjaFor protection against electric shock in low voltage systems residual current devices are commonly used. However, their proper operation can be interfered when high frequency earth fault current occurs. Serious hazard of electrocution exists then. In order to detect such a current, it is necessary to modify parameters of residual current devices, especially the operating point of their current transformer. The authors proposed...
-
A Comprehensive Analysis of Impedance of the Electrochemical Cell
PublikacjaA comprehensive impedance characteristics of two electrodes electrochemical cell has been pre sented. In this method a multisinusoidal current excitation signal is used. The change of potential of both the electrodes are all registered as a function of time. The proposed method gives the possibility of determining the impedance of both electrodes individually as well as the impedance of a twoelectrode system. Additional application...
-
Flow Boiling in Minigap in the Reversed Two-Phase Thermosiphon Loop
PublikacjaThe paper presents the results of experimental investigations of a model of a heat exchanger featuring a minigap, which is perceived as an evaporator for an inverted thermosiphon. The system works with a single component test fluid. The tested evaporator generates pumping power in the test loop in a way similar to the mammoth pump. The tests regarded a module of the heat exchanger, consisting of a hot leg and a cold leg with the...